The inputs are good for 240v.
On Oct 23, 2014 2:06 PM, "Nate Burke via Af" <[email protected]> wrote:

> I have a ticket into Packetflux support, but I thought someone here might
> have hooked one up.
>
> On the AC inputs for monitoring line/generator voltage/frequency. Are the
> 2 terminals on each AC input for hot/neutral wires?  I.E. only a single
> phase 120v system.  Or can you run 2 hots into each input, for a 2
> Wire120/240v system, and it will monitor each leg? Just wanted to ask
> before I hook it up wrong and release some magic smoke.
>