We had to set the timing a little longer so

the PLC did not see a failure with one ping drop


On 05/17/2017 01:25 PM, Jaime Solorza wrote:
Bridged and static IPs ...no Internet access. They are checking one PLC right now...

On May 17, 2017 12:09 PM, "Mitch Koep" <[email protected] <mailto:[email protected]>> wrote:

    I will assume all bridge mode with WDS enabled

    and router giving PLCs the IP or static assigned to PLCs??

    Mitch Koep

    218-851-8689 <tel:%28218%29%20851-8689> cell



    On 05/17/2017 01:02 PM, Jaime Solorza wrote:
    We have Rocket M5 and M9 as AP , and NanoBeams as Remotes.  The
    logs don't show reboots or other issues.  I think it might be PLC
    issue as well.

    On May 17, 2017 11:58 AM, "Mitch Koep" <[email protected]
    <mailto:[email protected]>> wrote:

        What radios and firmware? bridge or router mode?

        We had problems with the PLCs not radios

        Mitch Koep

        218-851-8689 <tel:218-851-8689> cell




        On 05/17/2017 10:36 AM, Jaime Solorza wrote:

            We have a SCADA network with Ubiquiti radios,
            toughswitches and Rockwell PLCs that are showing some
            timeouts. The links come back up on their own but wonder
            if the issue is radios or toughswitches?  Another
            engineer friend has noticed same thing with similar setup
            in system in Hobbs.  I have run diagnostics yet ...what
            should I look for? Thanks Jaime


-- Mitch Koep

        A Better Wireless
        218-851-8689 <tel:218-851-8689> cell



-- Mitch Koep

    A Better Wireless
    218-851-8689 <tel:%28218%29%20851-8689>  cell


--
Mitch Koep

A Better Wireless
218-851-8689 cell