Hi,

The server is now back online, after being unavailable for 5 hours
today, following an incident in one of the datacenters of OVH, our
hosting plateform. They explained the issue there:

http://travaux.ovh.com/?do=details&id=4871 (French)

English Google translation:

"We've had two cuts on this room. 

A first time was due to the problem on a circuit breaker of Bater, 
who jumped when testing generators. We 
have changed and we decided to work conducted 
to put 2 games by UPS with 2 bateries dijonctor 
for each inverter. Work is nearing completion, it 
do we have left is ... UPS has just blown up. 
Mismanagement of work. we should have started with this 
UPS and not finish. 

Deuxiemme cut was due to testing power generators with 
failover for multiple test requirements for ecological 
the DREAL. UPS hdst misinformation about the state 
of baterie, induquant remaining 80% while the bateries were 
apparently empty. The UPS has cut during failover 
POWER SOURCE 

http://travaux.ovh.net/?do=details&id=4656 
http://travaux.ovh.net/?do=details&id=3819 

This morning we have scheduled the work with EDF to build 
dual power RBX-2/RBX-4 from a new source. A 
cutoff of 8 seconds was expected. This cutoff level is 20000V 
cashed by UPS with a stock of energy on bateries and 
can generate power for 15 minutes. We do have some 
Cut on the third room 26 due to enocre dijonctor of bateries which once 
over blown. 2 things: work is underway to put 
2 dijonctor in parallel with 2 sets of bateries. but this problem 
is not normal. The first time the manufacturer, Eaton, diagnosed 
dijonctor failure and therefore we replaced it. Why 
dijonctor jumps when it is new? We have to find the origin 
the problem. 

We are currently en route back servers."