Hi, The server is now back online, after being unavailable for 5 hours today, following an incident in one of the datacenters of OVH, our hosting plateform. They explained the issue there:
http://travaux.ovh.com/?do=details&id=4871 (French) English Google translation: "We've had two cuts on this room. A first time was due to the problem on a circuit breaker of Bater, who jumped when testing generators. We have changed and we decided to work conducted to put 2 games by UPS with 2 bateries dijonctor for each inverter. Work is nearing completion, it do we have left is ... UPS has just blown up. Mismanagement of work. we should have started with this UPS and not finish. Deuxiemme cut was due to testing power generators with failover for multiple test requirements for ecological the DREAL. UPS hdst misinformation about the state of baterie, induquant remaining 80% while the bateries were apparently empty. The UPS has cut during failover POWER SOURCE http://travaux.ovh.net/?do=details&id=4656 http://travaux.ovh.net/?do=details&id=3819 This morning we have scheduled the work with EDF to build dual power RBX-2/RBX-4 from a new source. A cutoff of 8 seconds was expected. This cutoff level is 20000V cashed by UPS with a stock of energy on bateries and can generate power for 15 minutes. We do have some Cut on the third room 26 due to enocre dijonctor of bateries which once over blown. 2 things: work is underway to put 2 dijonctor in parallel with 2 sets of bateries. but this problem is not normal. The first time the manufacturer, Eaton, diagnosed dijonctor failure and therefore we replaced it. Why dijonctor jumps when it is new? We have to find the origin the problem. We are currently en route back servers."
_______________________________________________ Farsides mailing list - [email protected] Wiki: http://farsides.com/ List: http://farsides.com/ml/ Forum: http://farsides.com/forum/ Ideas: http://farsides.com/ideas/ Chat: http://farsides.com/chat/