AGM works well or LiFePo4 (lighter, smaller and more expensive, higher operating voltage so better for radio, pickier to charge properly)... Neither offgas so they're safe for in the home. AGM can be used down to 50% charge, lithium 80% without damage, so you have to compensate when comparing capacities (apples/oranges). (The days of lead are ending.)

I'd suggest that you define the battery type you want to use, then get a solar controller that is both RF quiet (duh) and can help manage the battery chemistry effectively.

LiFePo4 was my choice for portable/RV ops and the charger I use can charge from 9-20V (because it charges each cell individually at the appropriate voltage/current) so I can charge while driving between sites. It wasn't cheap to get started (battery, management board, charger[s]), but size and weight matters on the road (half the size, 1/3 the weight compared to lead). The radio prefers it to AGM (it's cleaner) from the slightly higher voltage. The lifespan of lead is 3-5 years, lithium is 10+ years and can be recharged MANY more times (factors when considering cost/year, lithium wins even though they cost more initially). Lithium maintains a charge much longer than lead if unused. My next move is to get a small solar charger; which will lead into more panels, time and expense (so I'm dawdling).

Learning curve: Lead charges fade over use, making it simple to know when to charge. Lithium goes full tilt, until it doesn't; so you want to monitor each cell and don't get to the cutoff voltage. The 'knee' on lithium is subtle.

WARNING: Battery chemistry with proper maintenance techniques can be a HUGE learning curve and there is a LOT of misinformation out there to filter out. I do not claim to be an expert, but I know some who are.

CAVEATS:

Some solar controller designs manage via the negative lead, which if the battery is also bonded to anything else (an RV), can be a BAD thing (momentarily exciting but smelly and potentially expensive). If the battery is not connected to anything while being charged (unlikely) it's safe. [Find a controller for your situation, both designs work but management via positive is overall safer.]

Some LiFePo4 bulk chargers (running through a BMS - Battery Management System device) are switcher supplies that generate RF noise (shouldn't be an issue with a quiet solar charger). Ask me how I know? At home, I use an Astron linear supply, no noise. If I use the switcher (rare), I'm not operating.

That, in a nutshell, are the high points of a month of online discussion with my battery guru.

Rick nhc


On 2/6/2017 10:53 AM, Matt Zilmer wrote:
You might look into CirKits SCC charge controllers. I use the SCCS3 here with two 50W 12V PV panels to keep the 75A-H station battery charged. It's an easy-to-build kit.

cirkits.com

73,

matt W6NIA


On 2/6/2017 10:37 AM, Harry Yingst via Elecraft wrote:
My son has my KX3 and I'm building a K2. Both of us have a set of solar panel that are capable of a lil over an amp at 12v

We are both looking for a battery idea and a method of hooking it to the solar panels to charge it .

Thank you

______________________________________________________________
Elecraft mailing list
Home: http://mailman.qth.net/mailman/listinfo/elecraft
Help: http://mailman.qth.net/mmfaq.htm
Post: mailto:[email protected]

This list hosted by: http://www.qsl.net
Please help support this email list: http://www.qsl.net/donate.html
Message delivered to [email protected]

Reply via email to