All
I have a piece of equipment falling under the scope of EN6010. To set the scene 
it is a low volume product, approx 0.5m cube, stainless steel enclosure and 
will sit on a bench in food cold storage areas. Mains lead connects via IP68 
connector.
It incorporates a SMPS  for universal mains operation ( current draw approx 
0.3A).

Because of problems ensuring  a reliable earth in some locations for its 
predecessor, I have specifically designed it to be Class2 (double insulated). 
Therefore safe for all markets.

Now, ironically, I am encountering some "unease" with the UK sales dept. After 
all everyone KNOWS that a metal box should be earthed. (I don't dismiss this 
attitude lightly because it is no doubt shared by some of the customer base.)  
Technically there is no problem with providing a 3-core cable and connecting up 
the earth conductor. And after all if 2 levels of protection is good, 3 levels 
is better.

Option 1 is obviously to stick with the design as is and educate 
sales/customers where necessary.

Option 2 is to provide a 3core product for the some markets and a 2core product 
for others. This goes against the original intention to have a universal 
product.

Is there an option 3? ie provide 3core cable and explain in the manual that 
product is designed to be safe without an earth but the earth may be fitted if 
desired. What about the square in square symbol?


I'm sure that I'm not the first to be looking at these questions. Any and all 
thoughts would be appreciated.
Best regards, Andy.

Andrew Wood
Engineer (Specials)

Land Instruments International
England





Please excuse following message automatically inserted by server........ 


This e-mail and its contents may be confidential, privileged and protected 
by law. Access is only authorised by the intended recipient. The contents 
of this e-mail may not be disclosed to, or used by, anyone other than the 
intended recipient, or stored or copied in any medium. If you are not the 
intended recipient, please advise the sender immediately.



-------------------------------------------
This message is from the IEEE EMC Society Product Safety
Technical Committee emc-pstc discussion list.

Visit our web site at:  http://www.ewh.ieee.org/soc/emcs/pstc/

To cancel your subscription, send mail to:
     [email protected]
with the single line:
     unsubscribe emc-pstc

For help, send mail to the list administrators:
     Michael Garretson:        [email protected]
     Dave Heald                [email protected]

For policy questions, send mail to:
     Richard Nute:           [email protected]
     Jim Bacher:             [email protected]

All emc-pstc postings are archived and searchable on the web at:
    No longer online until our new server is brought online and the old 
messages are imported into the new server.

Reply via email to