size=2>Checkpointing does NOT save operator set values like alarm setting PID
setting and the like.</FONT></SPAN></DIV>
<DIV><SPAN class=520334307-06042001><FONT face=Arial color=#0000ff
size=2></FONT></SPAN> </DIV>
<DIV><SPAN class=520334307-06042001><FONT face=Arial color=#0000ff size=2>This
would require an upload from the block, compound or station.</FONT></SPAN></DIV>
<DIV><SPAN class=520334307-06042001><FONT face=Arial color=#0000ff size=2>An ICC
driver script could do this on a timely interval. It is NOT performed
automatically.</FONT></SPAN></DIV>
<DIV><SPAN class=520334307-06042001><FONT face=Arial color=#0000ff
size=2>Uploads can be done from the Integrated Control Configurator itself. The
station upload is done from the Maint menu pick, Compund and block upload can be
performed from the upload pick in the center window in ICC.</FONT></SPAN></DIV>
<DIV><SPAN class=520334307-06042001><FONT face=Arial color=#0000ff
size=2></FONT></SPAN> </DIV>
<DIV><SPAN class=520334307-06042001><FONT face=Arial color=#0000ff size=2>Hope
this helps</FONT></SPAN></DIV>
<DIV><SPAN class=520334307-06042001><FONT face=Arial color=#0000ff
size=2></FONT></SPAN> </DIV>
<DIV><SPAN class=520334307-06042001>
<P><FONT face=Arial color=#000000 size=2>Ron Deen</FONT> <BR><FONT face=Arial
color=#000000 size=2>Foxboro Nederland N.V.</FONT> <BR><FONT face=Arial
color=#000000 size=2>Baarnschedijk 10</FONT> <BR><FONT face=Arial color=#000000
size=2>3741 LS Baarn</FONT> <BR><FONT face=Arial color=#000000 size=2>The
Netherlands</FONT> <BR><FONT face=Arial color=#000000 size=2>Phone:
+31(0)35-5484174</FONT> <BR><FONT face=Arial color=#000000
size=2>Fax: +31(0)35-5484175</FONT> <BR><FONT face=Arial
color=#000000 size=2>Web: www.foxboro.com</FONT> <BR><FONT
face=Arial color=#000000 size=2>e-mail: [EMAIL PROTECTED]</FONT>
</P></SPAN></DIV>
<BLOCKQUOTE dir=ltr style="MARGIN-RIGHT: 0px">
<DIV class=OutlookMessageHeader dir=ltr align=left><FONT face=Tahoma
size=2>-----Original Message-----<BR><B>From:</B> Marlon Mills
[mailto:[EMAIL PROTECTED]]<BR><B>Sent:</B> vrijdag 6 april 2001
4:27<BR><B>To:</B> [EMAIL PROTECTED]<BR><B>Subject:</B>
Checkpoint & Micro I/A<BR><BR></FONT></DIV>
<DIV><FONT face=Arial size=2>Hello all,</FONT></DIV>
<DIV><FONT face=Arial size=2>I'm working with 2 Micro I/As at ver 6.1 and
AW70 doing mainly sequence logic and Allen Bradley Flex I/O.</FONT></DIV>
<DIV><FONT face=Arial size=2></FONT> </DIV>
<DIV><FONT face=Arial size=2>Power losses and setpoint changes are occasional
and in order to save running settings a checkpoint is done before power
loss. Upon resumption of power and station startup, the system has
strange setpoints for example that were not there at the time of
checkpointing.</FONT></DIV>
<DIV><FONT face=Arial size=2></FONT> </DIV>
<DIV><FONT face=Arial size=2>Hints anyone ?</FONT></DIV>
<DIV><FONT face=Arial size=2></FONT> </DIV>
<DIV><FONT face=Arial size=2></FONT> </DIV>
<DIV><FONT face=Arial size=2>Marlon
Mills</FONT></DIV></BLOCKQUOTE></BODY></HTML>
</x-html>