Hi Kevin,
You must midify the .profile o script (go_dm) that run the x-sesion, this
file is in /opt/ia. In this file exist a line with the "jettool" reference,
you must insert a "#" sign in the line being.
Pedro,
-----Original Message-----
From: Kevin Fitzgerrell [SMTP:[EMAIL PROTECTED]]
Sent: Friday, January 28, 2000 4:50 PM
To: Foxboro DCS Mail List
Subject: Setting up PC with Exceed as Xterminal, "U" doesn't work?
I have set up a PC running Hummingbird Exceed for xterminal software. I
have no problem starting a display manager or any of the tools
(textedit, cmdtool, etc...) and all my graphics look normal. Only
problem is when I type the letter "U" or "u" in a field (or at the
command line in cmdtool) I don't get the letter, I just get a change
in the cursor. I know I've seen this before, but I can't remember a
fix. Thanks in advance for any help!
Kevin FitzGerrell