Kevin,
I finally got around to working on this problem again. Your suggestion to
connect the SWCH out parameter to the BCALCI parameter fixed my problem.
The system works as intended now. I looked into using the SSC as suggested
by Alex Johnson but in my case the downstream block is a PTC block which
does not support the SSC. One other little thing I noticed while working
on this is that there appears to be a bug in the Select page display for
SWCH blocks. It has a parameter called BCALCO which does not exist on the
SWCH block but it does not have the BCALC1 and BCALC2 parameters which do
exist.
Thanks for your help with this problem.
Cyrus
-----------------------------------------------------------------------