It is not currently possible to model general voltage dependent loads in 
MATPOWER. The best we can do currently is a combination of constant power and 
constant impedance, where the constant impedance is entered as a shunt 
impedance (columns GS and BS) in the bus matrix.

-- 
Ray Zimmerman
Senior Research Associate
419A Warren Hall, Cornell University, Ithaca, NY 14853
phone: (607) 255-9645




On Aug 17, 2011, at 9:18 AM, Lemke, André wrote:

> Hello,
> 
> how can a voltage-dependent load simulates in Matpower?
> 
> greetings
> 
> André Lemke
> 
> Fraunhofer-Institut für Umwelt-, Sicherheits- 
> und Energietechnik UMSICHT 
> Geschäftsfeld Energie-Effizienz-Technologien 
> Osterfelder Str. 3, 46047 Oberhausen
> 
> mailto:[email protected]
> 
> 

Reply via email to