For RATE_A, use 0 or Inf (they should result in the same answer). For the 
interface limits, use Inf (or -Inf) for unlimited flows.

-- 
Ray Zimmerman
Senior Research Associate
419A Warren Hall, Cornell University, Ithaca, NY 14853
phone: (607) 255-9645




On Mar 2, 2012, at 2:49 PM, Zhouxing Hu wrote:

> Dr. Zimmerman,
> 
> If I don't have MVA limit available for a branch, should I set RATE_A B and C 
> to '0' or '99999', or 'Inf'? I tried all of them and get different results by 
> solving ACOPF. 
> Also, how about interflow limit, eg. it is unlimited for positive direction 
> and -2000 MW for negative direction. Should I use ' -2000, Inf', '-2000, 0', 
> or '-2000, 99999', or anything else? 
> Thanks,
> 
> Zhouxing Hu
> 