Angelina,

OPF formulation should not have a slack bus.  As far as I know, Matpower (v
4.1)
opf does not optimize wrt tap and phase shifter settings.  You can always
derive
sensitivities wrt these settings and adjust them in an external loop.

I hope this makes sense,
Jovan

On Tue, Mar 3, 2015 at 11:50 AM, angelina sirri <[email protected]> wrote:

> Hello matpower users,
>
> I would be interested in implementing on load tap changers in an opf
> calculation. I searched in the archive but I couldn't find a clear help.
> How to change the tap in the transformer of the slack bus? Is it a change
> done in the mpc file or should I modify runopf code? Any instructions and
> clarifications would be valuable!
>
> Kind Regards,
> Angelina
>