Dear Siddique Tomal,
having constraints for bus voltages is only possible if you have flexibilities that allow you to keep those constraints. In a normal power flow you do not have these flexibilties, since active and reactive power is fixed at most buses. What you ask for is only possible with an OPF and is in fact exactly what the OPF is designed to do. Regards Leon Von: [email protected] [mailto:[email protected]] Im Auftrag von siddique tomal Gesendet: Freitag, 27. Januar 2017 13:33 An: [email protected] Betreff: Bus Voltage Constraints Dear all, i have a query about bus voltage constraints in normal power flow. I want to set a limit for every bus voltage (+-5%). So I’m asking help regarding this fact. It is just like 'vmax' and 'vmin' column in bus data matrix works only in optimal power flow. but i need this feature for normal power flow. Thanks