On Thu, 2003-04-03 at 21:39, David Mohorn wrote: > Hello - can you post the cfg for monitoring your SH2+ device? Thanks
Note that I am using Big Brother with bb-mrtg.pl for alerting from these devices. > Loadmibs: /usr/local/share/snmp/mibs/sa.mib Target[DG-temp]: hhmsSensorArrayTempDegree.1&hhmsSensorArrayTempDegree.1:[EMAIL PROTECTED] bb*host[DG-temp]: DG-SUB bb*svc[DG-temp]: temp bb*yellow[DG-temp]: 83 bb*red[DG-temp]: 88 MaxBytes[DG-temp]: 185 RouterUptime[DG-temp]: [EMAIL PROTECTED] Options[DG-temp]: Gauge noi Title[DG-temp]: Probe temperature gauge YLegend[DG-temp]: degrees F ShortLegend[DG-temp]: F Legend1[DG-temp]: F Legend2[DG-temp]: F Legend3[DG-temp]: F Legend4[DG-temp]: F LegendI[DG-temp]: F LegendO[DG-temp]: F PageTop[DG-temp]: <H1>Temperature</H1> <TABLE> <TR><TD>System:</TD><TD>Daffin Gin Substation Probe </TD></TR> </TABLE> #..................................................................... Target[DG-hum]: hhmsSensorArrayHumidityPercent.0&hhmsSensorArrayHumidityPercent.0:[EMAIL PROTECTED] bb*host[DG-hum]: DG-SUB bb*svc[DG-hum]: humidity bb*yellow[DG-hum]: 17:80 bb*red[DG-hum]: 12:85 MaxBytes[DG-hum]: 100 RouterUptime[DG-hum]: [EMAIL PROTECTED] Options[DG-hum]: Gauge noi Title[DG-hum]: Probe humidity gauge YLegend[DG-hum]: relative humidity ShortLegend[DG-hum]: % Legend1[DG-hum]: % Legend2[DG-hum]: % Legend3[DG-hum]: % Legend4[DG-hum]: % LegendI[DG-hum]: % LegendO[DG-hum]: % PageTop[DG-hum]: <H1>Humidity</H1> <TABLE> <TR><TD>System:</TD><TD> Daffin Gin Substation Probe </TD></TR> </TABLE> If you put the sensors in the other order, you have to swap the instances. I also have the following in my oid-mib-cache.txt file: hhmsSensorArrayTempDegree 1.3.6.1.4.1.3854.1.2.2.1.16.1.3 hhmsSensorArrayHumidityPercent 1.3.6.1.4.1.3854.1.2.2.1.17.1.3 > -----Original Message----- > From: [EMAIL PROTECTED] [mailto:[EMAIL PROTECTED] On > On Thu, 2003-04-03 at 10:22, Jason Humes wrote: > > Hi there, > > Does anyone know how I could monitor/graph temperature on a cisco 2950 > > switch? Thanks > > The WS-C2950-* doesn't have a temperature sensor. > > I use a sp2+ probe from Uptime Devices to get my temperatures. I've got > about 40 of them, scattered around the city. -- Daniel J McDonald, CCIE 2495, CNX Austin Energy -- Unsubscribe mailto:[EMAIL PROTECTED] Archive http://www.ee.ethz.ch/~slist/mrtg FAQ http://faq.mrtg.org Homepage http://www.mrtg.org WebAdmin http://www.ee.ethz.ch/~slist/lsg2.cgi