The Intra-building lightning tests in section 4 of GR-1089-CORE apply to 10baseT and 100baseT ports. If the product can be deployed at a customer premise, the 120V 25 amp power fault tests in section 4.5.16 also apply. There are also documentation requirements stating these ports are only intended for connection to intra-building wiring.
We regularly perform these tests and pass them on our 10baseT and 100baseT interfaces as part of our NEBS evaluations. Jim Jim Wiese NEBS Project Manager/Compliance Engineer ADTRAN, INC. 901 Explorer Blvd. P.O. Box 140000 Huntsville, AL 35814-4000 256-963-8431 256-963-8250 fax [email protected] > ---------- > From: Mitch Gaudyn[SMTP:[email protected]] > Sent: Thursday, April 06, 2000 9:05 AM > To: [email protected] > Subject: Lightning tests on Ethernet ports > > I am interested in finding out what lightning requirements exist on > Ethernet ports located on both CO and Network equipment. Also, if > anyone has done any testing on these ports, I would be interested in the > test methods and results. Thank you. > Mitch Gaudyn >