Citeren Vecheslav A Grebenschikov <[email protected]>:

Here are my configuration files:
---
srv:/usr/local/ups # cat etc/ups.conf
[npower]
driver = megatec
port = /dev/ttyS0
desc = "Srv"
battvolts = 1.8:2.1
battvoltmult = 18
lowbatt = 10
srv:/usr/local/ups #

Add
    offdelay = 1
    ondelay = 3

to the ups.conf file. Unfortunately, the default value of '0' is not accepted by older UPS implementations of the megatec protocol. Make sure to wait at least one minute after issuing this command. See also 'man 8 megatec'.

You could also try the 'blazer_ser' driver, which uses more conservative defaults here. See 'man 8 blazer' for more information on this driver.

Best regards, Arjen
--