Citeren Kelvin Ku <[email protected]>:

Note that the problematic unit, upsserv7, exhibits the USB disconnect behavior even when it's the only UPS connected to the host.

If possible, run it in debug mode

    /path/to/usbhid-ups -DD -a upsserv7

and watch the output when it (re)connects. Chances are that the device is reporting different serial numbers (or none at all) depending whether this is the first connection made or a later one. We've seen such erratic behavior before on other devices. This will make it impossible for the driver to reconnect. You'll be specifically interested in lines with "Serial Number" in them (and a few lines of context before and after it).

Best regards, Arjen
--
Please keep list traffic on the list


_______________________________________________
Nut-upsdev mailing list
[email protected]
http://lists.alioth.debian.org/mailman/listinfo/nut-upsdev