Seems as sensors stored in uncommon Oids,
currently unsupported.
Same way as adding support for new OS/Hardware.
Create Jira issue here:
https://jira.observium.org/secure/CreateIssue!default.jspa
<https://jira.observium.org/secure/CreateIssue%21default.jspa>
Make and attach full snmpdump from device as:
snmpwalk -v2c -c <community> -Cc --hexOutputLength=0 -Ih -ObentxU
<hostname> .1 > myagent.snmpwalk
snmpwalk -v2c -c <community> -Cc --hexOutputLength=0 -Ih -ObentxU
<hostname> .1.3.6.1.4.1 >> myagent.snmpwalk
If device not support SNMP version 2c, replace -v2c with -v1.
promise kumalo via observium wrote on 28.08.2023 12:16:
Hello
i am having trouble adding the new APC EPDU1132M to the observium.
The device is being added and recognised as an APC PDU, but there are
no power readings being recorded.
i have added an old model APC AP7854 B2 to observium and its works
perfectly, i can see the power readings.
i am running obversium CE 23.1.12493.
_______________________________________________
observium mailing list -- [email protected]
To unsubscribe send an email to [email protected]
--
Mike Stupalov,
Discord channel: https://discord.gg/GjpNXKWm8W
Observium Limited, https://observium.org
_______________________________________________
observium mailing list -- [email protected]
To unsubscribe send an email to [email protected]