Thank you very much, it works! среда, 15 июля 2020 г., 12:33:56 UTC+3 пользователь Egor Vasilyev написал: > > I use APC PowerNet MIB 4.2.6. My generator.yaml: > > modules: > template_acrd_602: > version: 3 > max_repetitions: 25 > retries: 3 > timeout: 30s > walk: > - coolingUnitStatusAnalogTableIndex > - coolingUnitStatusAnalogDescription > - coolingUnitStatusAnalogValue > > > I try: > # curl -sw '' ' > http://127.0.0.1:9116/snmp?module=template_acrd_602&target=hostname' > > And receive (the original output contains dozens of metrics, I shrank it): > coolingUnitStatusAnalogDescription{coolingUnitStatusAnalogDescription="Air > Filter Run Hrs",coolingUnitStatusAnalogTableIndex="44", > coolingUnitTableIndex="1"} 1 > coolingUnitStatusAnalogTableIndex{coolingUnitStatusAnalogTableIndex="44", > coolingUnitTableIndex="1"} 44 > coolingUnitStatusAnalogValue{coolingUnitStatusAnalogTableIndex="44", > coolingUnitTableIndex="1"} 4472 > > > And it's ok. But if I add a lookup section into generator.yaml like this: > > modules: > template_acrd_602: > version: 3 > max_repetitions: 25 > retries: 3 > timeout: 30s > walk: > - coolingUnitStatusAnalogTableIndex > - coolingUnitStatusAnalogDescription > - coolingUnitStatusAnalogValue > lookups: > - source_indexes: [coolingUnitStatusAnalogTableIndex] > lookup: coolingUnitStatusAnalogDescription > > > I expect to receive an output something like this: > > coolingUnitStatusAnalogDescription{coolingUnitStatusAnalogDescription="Air > Filter Run Hrs",coolingUnitStatusAnalogTableIndex="44", > coolingUnitTableIndex="1"} 1 > coolingUnitStatusAnalogTableIndex{coolingUnitStatusAnalogDescription="Air > Filter Run Hrs"coolingUnitStatusAnalogTableIndex="44", > coolingUnitTableIndex="1"} 44 > coolingUnitStatusAnalogValue{coolingUnitStatusAnalogDescription="Air > Filter Run Hrs"coolingUnitStatusAnalogTableIndex="44", > coolingUnitTableIndex="1"} 4472 > > > But actually I receive: > coolingUnitStatusAnalogDescription{coolingUnitStatusAnalogDescription="", > coolingUnitStatusAnalogTableIndex="44",coolingUnitTableIndex="1"} 1 > coolingUnitStatusAnalogTableIndex{coolingUnitStatusAnalogDescription="", > coolingUnitStatusAnalogTableIndex="44",coolingUnitTableIndex="1"} 44 > coolingUnitStatusAnalogValue{coolingUnitStatusAnalogDescription="", > coolingUnitStatusAnalogTableIndex="44",coolingUnitTableIndex="1"} 4472 > > > What am I doing wrong? Help please. Thank you! > > OID description you could get on web site > <https://cric.grenoble.cnrs.fr/Administrateurs/Outils/MIBS/?oid=coolingUnitStatusAnalogTableIndex> > >
-- You received this message because you are subscribed to the Google Groups "Prometheus Users" group. To unsubscribe from this group and stop receiving emails from it, send an email to [email protected]. To view this discussion on the web visit https://groups.google.com/d/msgid/prometheus-users/d9fe594a-6f15-44d8-a716-bd7656693caeo%40googlegroups.com.