Hi Ron, Here is what I would do.
1. install a amp hr meter without this you have no idea of what is going in/out. So when they mention the batteries drop rapidly to 22.8, they can now see how many amps are going out. 2. record voltages to 2 decimal places of each battery when these anomalies occur. 3. record amps into battery when doing eq/charge and I agree with John, Jay Peltz Power _______________________________________________ List sponsored by Home Power magazine List Address: RE-wrenches@lists.re-wrenches.org Options & settings: http://lists.re-wrenches.org/options.cgi/re-wrenches-re-wrenches.org List-Archive: http://lists.re-wrenches.org/pipermail/re-wrenches-re-wrenches.org List rules & etiquette: www.re-wrenches.org/etiquette.htm Check out participant bios: www.members.re-wrenches.org