Hi Ron,

Here is what I would do.

1. install a amp hr meter
without this you have no idea of what is going in/out.  So when they mention 
the batteries drop rapidly to 22.8, they can now see how many amps are going 
out.
2. record voltages to 2 decimal places of each battery when these anomalies 
occur.

3. record amps into battery when doing eq/charge

and I agree with John,

Jay