Bug#373631: nut: Strange status : OL CHRG OFF
I correct myself: this has already been fixed in 2.0.3...so updating your system will solve this.2006/7/4, Arnaud Quette <[EMAIL PROTECTED] >:tag 373631 + upstreamthankSalut Fred, 2006/6/14, Frederic Massot <[EMAIL PROTECTED]>: Package: nutVersion: 2.0.2-2Severity: normalHi,After a break of electricity, an UPS (MGE Evolution 800) iswith the status: OL CHRG OFFAccording to the source code (drivers/newhidups.h): OL -> one lineCHRG -> chargingOFF -> ups is off !!?though having a status filled with " OL CHRG OFF" is possible (OFF means for MGE that we do not power the output), in your case, you're facing a bug that has been solved for the upcoming 2.0.4.Arnaud-- Linux / Unix Expert - MGE UPS SYSTEMS - R&D DptNetwork UPS Tools (NUT) Project Leader - http://www.networkupstools.org/ Debian Developer - http://people.debian.org/~aquette/OpenSource Developer - http://arnaud.quette.free.fr/ -- Linux / Unix Expert - MGE UPS SYSTEMS - R&D DptNetwork UPS Tools (NUT) Project Leader - http://www.networkupstools.org/ Debian Developer - http://people.debian.org/~aquette/OpenSource Developer - http://arnaud.quette.free.fr/
Bug#373631: nut: Strange status : OL CHRG OFF
tag 373631 + upstreamthankSalut Fred,2006/6/14, Frederic Massot <[EMAIL PROTECTED]>: Package: nutVersion: 2.0.2-2Severity: normalHi,After a break of electricity, an UPS (MGE Evolution 800) iswith the status: OL CHRG OFFAccording to the source code (drivers/newhidups.h): OL -> one lineCHRG -> chargingOFF -> ups is off !!?though having a status filled with " OL CHRG OFF" is possible (OFF means for MGE that we do not power the output), in your case, you're facing a bug that has been solved for the upcoming 2.0.4.Arnaud-- Linux / Unix Expert - MGE UPS SYSTEMS - R&D DptNetwork UPS Tools (NUT) Project Leader - http://www.networkupstools.org/ Debian Developer - http://people.debian.org/~aquette/OpenSource Developer - http://arnaud.quette.free.fr/
Bug#373631: nut: Strange status : OL CHRG OFF
Package: nut Version: 2.0.2-2 Severity: normal Hi, After a break of electricity, an UPS (MGE Evolution 800) is with the status: OL CHRG OFF According to the source code (drivers/newhidups.h): OL -> one line CHRG -> charging OFF -> ups is off !!? The UPS is on and run, it is not off. It misses in documentation an explanation of the various status. $ upsc [EMAIL PROTECTED] battery.charge: 100.0 battery.charge.low: 30 battery.runtime: 01250 battery.voltage: 027.4 battery.voltage.nominal: 024.0 driver.name: mge-utalk driver.parameter.port: /dev/ttyS0 driver.version: 2.0.2 driver.version.internal: 0.85 input.frequency: 49.00 input.transfer.boost.low: 184.0 input.transfer.high: 265.0 input.transfer.low: 184.0 input.transfer.trim.high: 265.0 input.voltage: 231.7 output.current: 001.3 output.voltage: 231.7 ups.delay.shutdown: 020 ups.delay.start: 001 ups.firmware: unknown ups.id: Evolutio 800 0 ups.load: 031.0 ups.mfr: MGE UPS SYSTEMS ups.model: Evolution 800 ups.status: OL CHRG OFF ups.test.interval: 10080 Regards. -- System Information: Debian Release: testing/unstable APT prefers testing APT policy: (500, 'testing'), (500, 'stable') Architecture: i386 (i686) Shell: /bin/sh linked to /bin/bash Kernel: Linux 2.6.15 Locale: [EMAIL PROTECTED], [EMAIL PROTECTED] (charmap=ISO-8859-15) Versions of packages nut depends on: ii adduser 3.85 Add and remove users and groups ii debconf [debconf-2.0] 1.4.72 Debian configuration management sy ii libc6 2.3.6-7GNU C Library: Shared libraries nut recommends no packages. -- debconf information: nut/change_system_user: nut/major_conf_changes: * nut/major_upstream_changes: true nut/remove_debian_conf: nut/2_0_upstream_changes: -- To UNSUBSCRIBE, email to [EMAIL PROTECTED] with a subject of "unsubscribe". Trouble? Contact [EMAIL PROTECTED]