Re: [RE-wrenches] Combining Enphase M190 and M215 on same circuit
Jason, The M190 requires using a 15-amp (maximum) branch circuit. As long as the total current from both types of inverters doesn't exceed 12 amps (80% of 15), there should not be a problem in mixing the inverters. The combination you are proposing is only 8.6 amps -- it should be fine. Kent Osterberg Blue Mountain Solar, Inc. www.bluemountainsolar.com On 5/18/2013 3:26 PM, Jason Szumlanski wrote: Is there any reason I can't do this? I have an existing string of 3 M190's and want to add 7 M215's. I plan to tie into the same j-box, which has #10 going to a fusible disconnect and a supply side tap. I'll just have to change the fuse rating. Any comm issues reported with this setup? Jason Szumlanski Fafco Solar ___ List sponsored by Home Power magazine List Address: RE-wrenches@lists.re-wrenches.org Change email address settings: http://lists.re-wrenches.org/options.cgi/re-wrenches-re-wrenches.org List-Archive: http://lists.re-wrenches.org/pipermail/re-wrenches-re-wrenches.org List rules etiquette: www.re-wrenches.org/etiquette.htm Check out participant bios: www.members.re-wrenches.org ___ List sponsored by Home Power magazine List Address: RE-wrenches@lists.re-wrenches.org Change email address settings: http://lists.re-wrenches.org/options.cgi/re-wrenches-re-wrenches.org List-Archive: http://lists.re-wrenches.org/pipermail/re-wrenches-re-wrenches.org List rules etiquette: www.re-wrenches.org/etiquette.htm Check out participant bios: www.members.re-wrenches.org
Re: [RE-wrenches] Combining Enphase M190 and M215 on same circuit
Hi Jason, You can do that, but will need to maintain the 15A limit of the M190s. For a single-phase, 240V application, with 3 M190s (3*0.8A = 2.4A,) you can install up to 10 M215s. On Sat, May 18, 2013 at 3:26 PM, Jason Szumlanski ja...@fafcosolar.comwrote: Is there any reason I can't do this? I have an existing string of 3 M190's and want to add 7 M215's. I plan to tie into the same j-box, which has #10 going to a fusible disconnect and a supply side tap. I'll just have to change the fuse rating. Any comm issues reported with this setup? Jason Szumlanski Fafco Solar ___ List sponsored by Home Power magazine List Address: RE-wrenches@lists.re-wrenches.org Change email address settings: http://lists.re-wrenches.org/options.cgi/re-wrenches-re-wrenches.org List-Archive: http://lists.re-wrenches.org/pipermail/re-wrenches-re-wrenches.org List rules etiquette: www.re-wrenches.org/etiquette.htm Check out participant bios: www.members.re-wrenches.org -- Cordially, *Nick Soleil* *Field Applications Engineer * *Enphase Energy* Mobile: (707) 321-2937 ** *Enphase Commercial Solar.* *Limitless.*http://www.enphase.com/commercial?utm_source=emailutm_medium=sigutm_campaign=Comm2012 * *http://www.enphase.com/commercial?utm_source=emailutm_medium=sigutm_campaign=Comm2012 1420 North McDowell Petaluma, CA 94954 www.enphase.com http://www.enphaseenergy.com/ P: (707) 763-4784 x7267 F: (707) 763-0784 E: nsol...@enphaseenergy.com [image: nabcep logo] Certified Solar PV Installer #03262011-300 “Don’t get me wrong: I love nuclear energy! It’s just that I prefer fusion to fission. And it just so happens that there’s an enormous fusion reactor safely banked a few million miles from us. It delivers more than we could ever use in just about 8 minutes. And it’s wireless! .” - William McDonough This email message is for the sole use of the intended recipient(s) and may contain confidential and/or privileged information. If you are not an intended recipient, you may not review, use, copy, disclose or distribute this message. If you received this message in error, please contact the sender by reply email and destroy all copies of the original message. image002.jpg___ List sponsored by Home Power magazine List Address: RE-wrenches@lists.re-wrenches.org Change email address settings: http://lists.re-wrenches.org/options.cgi/re-wrenches-re-wrenches.org List-Archive: http://lists.re-wrenches.org/pipermail/re-wrenches-re-wrenches.org List rules etiquette: www.re-wrenches.org/etiquette.htm Check out participant bios: www.members.re-wrenches.org
Re: [RE-wrenches] Lorentz Pumps
We have 1 Lorentz installation in Haiti and about 9 in West Africa - pumping around 10,000 gpd. Started using them a few years ago because we were having lots of problems with Grundfos. To date, I believe we've had problems with 1 controller and 1 pump. (not sure, but a wiring error on the part of our local techs might have caused one of these problems) We're now buying from American West Windmill and Solar in TX (800530-4744) and have had good service from them. For our next round of systems, we'll probably be looking at Sunpumps as well. Jeff Lahl | Project Director Solar Electric Light Fund | www.self.org p 808-874-5706 f 808-874-5706 energy is a human right™ Change a life.Change the world. From: Ray Walters r...@solarray.com To: RE-wrenches re-wrenches@lists.re-wrenches.org Sent: Saturday, May 18, 2013 1:41 PM Subject: [RE-wrenches] Lorentz Pumps Greetings Wrenchies; I have had a few inquiries for larger flow rate pumps, and was wondering what the latest on Lorentz pumps was. They show some commercial models with high flow rates (30,000gpd) but I haven't gotten any response from the company directly. I have three questions: Are there any good in country distributors? are they worth giving a try? and finally, is anyone actually selling any solar pumps, or just taking a lot of phone calls that ultimately lead no where (like us)? Thanks in advance as always, -- R.Ray Walters CTO, Solarray, Inc Nabcep Certified PV Installer, Licensed Master Electrician Solar Design Engineer 303 505-8760 ___ List sponsored by Home Power magazine List Address: RE-wrenches@lists.re-wrenches.org Change email address settings: http://lists.re-wrenches.org/options.cgi/re-wrenches-re-wrenches.org List-Archive: http://lists.re-wrenches.org/pipermail/re-wrenches-re-wrenches.org List rules etiquette: www.re-wrenches.org/etiquette.htm Check out participant bios: www.members.re-wrenches.org___ List sponsored by Home Power magazine List Address: RE-wrenches@lists.re-wrenches.org Change email address settings: http://lists.re-wrenches.org/options.cgi/re-wrenches-re-wrenches.org List-Archive: http://lists.re-wrenches.org/pipermail/re-wrenches-re-wrenches.org List rules etiquette: www.re-wrenches.org/etiquette.htm Check out participant bios: www.members.re-wrenches.org
Re: [RE-wrenches] Lorentz Pumps
Interesting about the licensed pump installer, because in New Mexico there is not a license. I've been installing PV pumping systems since 1988, so I tire easily now when companies won't work with me, because I'm not qualified. I actually installed some of the Mono hand crank and electric powered pumps in Morocco before it was ETA or Lorentz. I'll talk to Genpro on Monday. Thanks everybody, R.Ray Walters CTO, Solarray, Inc Nabcep Certified PV Installer, Licensed Master Electrician Solar Design Engineer 303 505-8760 On 5/18/2013 6:19 PM, Mac Lewis wrote: Hello Ray, We have had success selling solar pumps, but nothing in the 30,000 gpd category. Unfortunately, as I understand it, Lorentz will not sell to anyone that is not a licensed pump installer. You may talk to GenPro at http://www.genproenergy.com/lorentz-submersible-pumps.html to get the latest about Lorentz, or maybe team up with a licensed pump installer and do the solar part. We have had great results with the Grundfos SQFlex system for anything that we have installed and haven't found the need to specify a Lorentz. Good Luck On Sat, May 18, 2013 at 5:41 PM, Ray Walters r...@solarray.com mailto:r...@solarray.com wrote: Greetings Wrenchies; I have had a few inquiries for larger flow rate pumps, and was wondering what the latest on Lorentz pumps was. They show some commercial models with high flow rates (30,000gpd) but I haven't gotten any response from the company directly. I have three questions: Are there any good in country distributors? are they worth giving a try? and finally, is anyone actually selling any solar pumps, or just taking a lot of phone calls that ultimately lead no where (like us)? Thanks in advance as always, -- R.Ray Walters CTO, Solarray, Inc Nabcep Certified PV Installer, Licensed Master Electrician Solar Design Engineer 303 505-8760 tel:303%20505-8760 ___ List sponsored by Home Power magazine List Address: RE-wrenches@lists.re-wrenches.org mailto:RE-wrenches@lists.re-wrenches.org Change email address settings: http://lists.re-wrenches.org/options.cgi/re-wrenches-re-wrenches.org List-Archive: http://lists.re-wrenches.org/pipermail/re-wrenches-re-wrenches.org List rules etiquette: www.re-wrenches.org/etiquette.htm http://www.re-wrenches.org/etiquette.htm Check out participant bios: www.members.re-wrenches.org http://www.members.re-wrenches.org -- Mac Lewis * Yo solo sé que no sé nada. -Sócrates * ___ List sponsored by Home Power magazine List Address: RE-wrenches@lists.re-wrenches.org Change email address settings: http://lists.re-wrenches.org/options.cgi/re-wrenches-re-wrenches.org List-Archive: http://lists.re-wrenches.org/pipermail/re-wrenches-re-wrenches.org List rules etiquette: www.re-wrenches.org/etiquette.htm Check out participant bios: www.members.re-wrenches.org ___ List sponsored by Home Power magazine List Address: RE-wrenches@lists.re-wrenches.org Change email address settings: http://lists.re-wrenches.org/options.cgi/re-wrenches-re-wrenches.org List-Archive: http://lists.re-wrenches.org/pipermail/re-wrenches-re-wrenches.org List rules etiquette: www.re-wrenches.org/etiquette.htm Check out participant bios: www.members.re-wrenches.org