Stefano,
I think your intention is not only to protect Environments but to
enable/disable omsets.
Take a look at the following extract of an Env-Configuration:
dmcmd chng_env
dmcmd protect value 2
dmcmd disable omsets
== $DMNAME DMName1 enable omsets
== $DMNAME DMName1 unprotect value 2
==
G'day list,
Has anyone had any success in using 51D's with 4.2Gb external SCSI system
disks? Rumour has it, it's supposed to be possible - according to B0400PT
anyway.
I've Day Zeroed it, but I can't get it to boot. And yes, I have changed the
altdisk (originally raid) device label. It
Kevin,
Try the following web address. It has information about Sun's Snapshot utility.
http://www.thecassandraproject.org/misc/snapshot.pdf
Jim Kahlden
[EMAIL PROTECTED]
Lower Colorado River Authority
Fayette Power Project
6549 Power Plant Road
La Grange, TX 78945
(979) 249-8514 (Ph)
Hi Chris,
Yes, your message is in the archive:
http://www.mail-archive.com/foxboro@lists.thecassandraproject.org/msg00281.h
tml
I recommend reading Chris's note as it gives a detailed procedure. Kevin
asked about the 50-series, but Chris also gave instructions for the AW70.
Duc
--
Duc M. Do
Kevin.
If you would rather do your screen dump from the command prompt (or in a
script), try /usr/openwin/bin/xwd -root -out foo.xwd. This will create a
file of the root window of the AW/WP that you are logged into named
foo.xwd.
If you need the image file in a different format, try
Hello Nic
You don't say which release you day 0'd onto the drive. What was
the panic message ? Was it bad root or could not mount root ?
Did you check /etc/system for rootdev etc. ?
If the system reboots too fast to see the message, at the OK
prompt type boot kadb and it will the system at
My
info:
Ray W. Schlunk Account manager
Foxboro Nederland N.V. (as of 1 october 2001 this
will be Invensys Systems N.V.)
Tel: +31 (0)35 54
84 127Fax:
+31 (0)35 54 23 124 Mobile: +31 (0)6 53
96 2000
e-mail
[EMAIL PROTECTED]
I am a sales
person and
To my knowledge, the D box only supports RAID solutions as an external SCSI
drive configuration.
The System Administration Guide (B0193ND, Rev J) makes note of the external
SCSI drives will be supported in future releases. Since the guide was
provided with the 6.3 base level software it is
It's always a good thing to check you system load before and during an
upload. Look at the idle time and the free RAM.
Regards,
Alex Johnson
10707 Haddington
Houston, TX 77043
713.722.2859 (office)
713.722.2700 (switchboard)
713.932.0222 (fax)
[EMAIL PROTECTED] mailto:[EMAIL PROTECTED]
We have had this same problem for over 2 years now. Various field service
people and TAC have looked at it and been unable to determine the root of
the problem. We have upgraded our RAM, upgraded our hard drives all to no
avail. So far Foxboro has been little to no help in resolving the
We use the fashionable freeware/shareware program called xv.
It is a great X-Window snapshot and image editing program.
This program allows you to capture an X-window, and save it in almost any
image format.
You can install the package as follows (assuming Solaris 2.5):
1. Download from:
hi
first of all thank's everybody for suggestions
My real intention is to have same function on same displays both on
AW host PX Xterm. The only thing is to avoid the access from Xterm
to a given Environment which is free on AW host
I tried with == xtermdmname> dmcmd passwd in environment
hi list
pardon me if you already got this
but i was thinking that since i sent this on a weekend, maybe somehow the
message just did not get through
meanwhile, i urgently need the information
once again, sorry
and thanks for the replies
best regards,
J. M. Saputra
- Original Message -
13 matches