be to
communicate to the ControlLogix as a PLC-5. This would require a little bit
of configuration on the Rockwell side. I hope this is helpful.
Regards,
Jason
___
Jason Wright
Regional Technical Specialist
ControlSoft
(216) 397-3900 x201
A-B ControlLogix PLC's
Many Foxboro customers
:
OUT = [100/(PBAND INT s)] [(SPLLAG INT s+1) SPT - (INT s+1) MEAS]
In I-only, the PID algorithm is as follows:
OUT = [1/(INT s)] [SPT-MEAS]
Regards,
Jason
Jason Wright
Regional Technical Specialist
ControlSoft, Inc.
(216) 397-3900 x201