RE: PLC Question

2001-09-12 Thread Jason Wright
be to communicate to the ControlLogix as a PLC-5. This would require a little bit of configuration on the Rockwell side. I hope this is helpful. Regards, Jason ___ Jason Wright Regional Technical Specialist ControlSoft (216) 397-3900 x201 A-B ControlLogix PLC's Many Foxboro customers

RE: PIDA Blocks with I-only Control

2001-08-22 Thread Jason Wright
: OUT = [100/(PBAND INT s)] [(SPLLAG INT s+1) SPT - (INT s+1) MEAS] In I-only, the PID algorithm is as follows: OUT = [1/(INT s)] [SPT-MEAS] Regards, Jason Jason Wright Regional Technical Specialist ControlSoft, Inc. (216) 397-3900 x201 -Original Message- From: [EMAIL PROTECTED