Re: [MBZ] OT residential air conditioner issue

2021-07-24 Thread Mitch Haley via Mercedes
On 2021-07-23 16:11, Kevin Kraly via Mercedes wrote: We just had our A coil, lines and outdoor A/C unit replaced a couple months ago. Once it was put back together, air flow wasn’t the same as before. When they went underneath the house to check things out, they found that excess condensation

Re: [MBZ] OT residential air conditioner issue

2021-07-23 Thread Mitch Haley via Mercedes
My A coil has two drains. The primary is about 1/2 below the safety. The primary is trapped and plumbed to a safe drain (in my case the condensate pump for my furnace). The secondary is left wide open, if you ever see water there the main drain is plugged. On 2021-07-23 17:17, Meade Dillon

Re: [MBZ] OT residential air conditioner issue

2021-07-23 Thread Peter Frederick via Mercedes
Check to make sure you don't have a leak in the delivery side blowing on the return duct, as a cold wall on the return will cause condensation on the inside. Only thing I can think of other than a plumbing leak upstairs that is somehow making it's way into the return. Just had another thought,

Re: [MBZ] OT residential air conditioner issue

2021-07-23 Thread Allan Streib via Mercedes
Agreed, if it's condensation it has to be coming from the cold air side somhow. I've never seen condensation on the return air side, no matter how humid it is, and I don't think it's possible. That's room-temperature air coming back to be cycled through the evaporator again. Allan On Fri, Jul

Re: [MBZ] OT residential air conditioner issue

2021-07-23 Thread Meade Dillon via Mercedes
When the AC is in operation, on my AC, the cold A coil in the air handler will produce a lot of condensate dripping from it, as the warm air hits the cold coils. There is a pan below the coil, which has a drain outside the house. Perhaps your drain is plugged, so the water has found another

Re: [MBZ] OT residential air conditioner issue

2021-07-23 Thread Kevin Kraly via Mercedes
We just had our A coil, lines and outdoor A/C unit replaced a couple months ago. Once it was put back together, air flow wasn’t the same as before. When they went underneath the house to check things out, they found that excess condensation had rusted out the bottom of the air handler and a

[MBZ] OT residential air conditioner issue

2021-07-23 Thread Randy Bennell via Mercedes
My house has a basic HVAC system. We have a gas fired furnace in the basement and central air installed with the furnace. The evaporator A coil sits in the warm air plenum above the furnace. The Condenser sits outside by the back door. The whole setup of furnace and air conditioner is Lennox