OK, I just backported this bug fix to the testing branch.
John, could you please check that it is now showing the correct values
for your UPS? You can get the fixed version from SVN:
svn co svn://svn.debian.org/svn/nut/branches/Testing
then build as usual (./configure --with-drivers newhidups;
On Sat, Mar 04, 2006 at 01:55:41PM -0400, Peter Selinger wrote:
OK, I just backported this bug fix to the testing branch.
John, could you please check that it is now showing the correct values
for your UPS? You can get the fixed version from SVN:
svn co
On 3/5/06, John Gruenenfelder [EMAIL PROTECTED] wrote:
The values look much better now. The only one which looks a little off is:
battery.voltage: 27.8
battery.voltage.nominal: 24.0
But, frankly, I don't know if that's actually a problem. The UPS seems to be
running just fine so I'm