Telecordia/Bellcore's GR-1275-CORE covers Central Office Installation
Requirements.

Section 13 is titled Workmanship Requirements- Cabling     R13-81 calls for
minimum bending radius per Figure 13-34; power cables 12X the cable
Diameter
Section 14 is titled Workmanship Requirements-Wiring       R14-89 says the
bending radius of power and armored cable not less than 5x the cable
diameter

Neither section defines Power cables to help determine if our application
fits.  This is for design of shelf to shelf power cable hookup.

Any comments would be appreciated as long as it supports the reasonable 5X
bending radius.