-Original Message-
From: Trond Hasle Amundsen [mailto:t.h.amund...@usit.uio.no]
Sent: 25 June 2010 18:20
To: Nagios Users List
Subject: Re: [Nagios-users] check_openmanage: Use of uninitialized value in
sprintf at /usr/lib64/nagios/plugins/check_openmanage
Max Williams max.willi...@mflow.com
Max Williams max.willi...@mflow.com writes:
Here is the output, the inactive temperature probe is sorted but the
missing EMM still produces an alert:
OK | 1:1:0:1 | Temperature Probe 1 in enclosure 3 [MD1000] is Inactive
This one works as expected :)
OK | 1:1:0:2 |
: [Nagios-users] check_openmanage: Use of uninitialized value in
sprintf at /usr/lib64/nagios/plugins/check_openmanage
Max Williams max.willi...@mflow.com writes:
Here is the output, the inactive temperature probe is sorted but the
missing EMM still produces an alert:
OK | 1:1:0:1
Max Williams max.willi...@mflow.com writes:
Excellent, sorted, everything reports as OK now.
Good. I'll try to make a release with these changes in the next couple
of days.
Thanks so much Trond, amazing support and an amazingly useful plugin!
Glad you like it, Max. Thanks for reporting this
Hi,
After adding more storage to a couple of our servers we are getting this error:
[r...@host ~]# /usr/lib64/nagios/plugins/check_openmanage -C password -b
ctrl_driver=0,1,2 -b ctrl_fw=0,1,2 -b intr=0 -H host2
Temperature Probe 1 in enclosure 3 [MD1000] is Inactive C at ( max)
EMM 1 in
Max Williams max.willi...@mflow.com writes:
Hi,
After adding more storage to a couple of our servers we are getting this
error:
[r...@host ~]# /usr/lib64/nagios/plugins/check_openmanage -C password -b
ctrl_driver=0,1,2 -b ctrl_fw=0,1,2 -b intr=0 -H host2
Temperature Probe 1 in
need anything else.
Best Regards,
Max Williams
-Original Message-
From: Trond Hasle Amundsen [mailto:t.h.amund...@usit.uio.no]
Sent: 25 June 2010 16:02
To: Nagios Users List
Subject: Re: [Nagios-users] check_openmanage: Use of uninitialized value in
sprintf at /usr/lib64/nagios/plugins
Max Williams max.willi...@mflow.com writes:
Both of the new enclosures show the same output so perhaps these just
have a different configuration to the others we have here.
Yes. I suspect that the is related to one EMM not being installed. My
guess is that the inactive temperature sensor is