Re: DS3 Lightning

2000-06-13 Thread Bruce Touzel
What I learned from a test lab is the RBOC's have no interest in surging interfaces using coaxial cables. Joe Finlayson wrote: I am hearing mixed opinions of whether a DS3 Coax interface falls under the scope of interfaces to be subjected to GR-1089 4.5.9 Intrabuilding Lightning

RE: DS3 Lightning

2000-06-13 Thread Don House
One rarely used but real application is where the DS3 coax is run between two adjacent central offices across an alley. This was the case in Chicago where the DS3 was a link between ATT Long Lines and Illinois Bell. Because of possible ground loops the coax was grounded only at one end.

Re: DS3 Lightning

2000-06-13 Thread Bruce Touzel
This is also common in UK where British Telecom for example, will request that your E3 interface be able to ground or float the bnc shield. Don House wrote: One rarely used but real application is where the DS3 coax is run between two adjacent central offices across an alley. This was the