Re: [RE-wrenches] Just getting old?

2023-05-22 Thread Jerry Shafer via RE-wrenches
Bill You do need to verify that you also have No current, l see this quite a few times where modules have failed just to find a shorted inverter or damaged conduit where one wire overheats cause unknown and the cascade is they all melt together and it's such a great short that voltage is near

Re: [RE-wrenches] Just getting old?

2023-05-22 Thread Chris Daum via RE-wrenches
We haven’t sold these modules, but here’s some information: https://www.mitsubishielectricsolar.com/warranty-information/ Good luck! Chris Daum Oasis Montana Inc. 406-777-4309 or 4321 406-777-4309 fax www.oasismontana.com From: RE-wrenches On Behalf Of

Re: [RE-wrenches] Just getting old?

2023-05-22 Thread Dave Angelini Offgrid Solar via RE-wrenches
Bill, I remember the warranty was not great and the ones I had experience were not top Tier. I am thinking dumb looks are still free and a Seventeen year old installation is going to be more free time for you. I hope I am wrong, good luck! Dave Angelini Offgrid Solar "we go where powerlines

[RE-wrenches] Just getting old?

2023-05-22 Thread Bill Battagin via RE-wrenches
I went back to this array, removed all J-box covers and tested for Voc.  The majority of the PVs were ~ 9.5Voc, about 5 were ~19 Voc, 3 were 0 (that's zero) Voc .  The diodes are in an encapsulant.  The label says Voc = 22V. Another array of Mitsubishi panels takes a dive.             Anybody