It's a square wave which a transformer would clean up.  The drop wouldn't change and a buck-boost would up the voltage for the end-point.

On 7/8/21 7:15 AM, Steve Jones wrote:
We are considering moving our APCs down to the bottom of some of the grain elevators we have our enclosures up top of. There are a multitute of reasons for this, right wrong or indifferent.

The concern i have is the voltage drop. The output of APC UPS as I understand is not pure sine wave, but a square wave. Will this impact voltage drop calculations?

-- 