Well phooey.. a lot of this contradicts what my well-pay grounding expert, and well-recommended from to big EOCs in my area has to say about it. At least the part of welding to the tower.
I AM glad I asked and could see certainly see how a guy wire under tension could “break / cut” while cad-welding. So, in a typical guyed scenario (let’s say 4 levels of guys for example), I have turnbuckles attached to the guy “Flange/gusset – whatever you want to call it & deadends connecting the guy wires to the turnbuckles, the turnbuckles going through a hole in the gussets would not seem to be a good connection, so attaching the ground wire just to the gusset I think would be “weak” grounding. If the guy wires were to continue past the deadend, pass the turnbuckles, then it could connect to the plate, but how, if the cadwelding will burn through the guy wire. Paul From: Af [mailto:[email protected]] On Behalf Of George Skorup (Cyber Broadcasting) Sent: Monday, March 23, 2015 8:42 PM To: Subject: Re: [AFMUG] Cad welding expert advice needed :) Nope, not close enough to get hit. Just wind vibration as far as I can tell. Always broken near the wire clamps. If the ground wire was stranded and could flex, then it probably wouldn't break. At least that's my theory. Can't hurt to try. On 3/23/2015 7:25 PM, Erich Kaiser wrote: Why are they breaking? Is the farmer hitting them? Erich Kaiser North Central Tower [email protected]<mailto:[email protected]> Office: 630-621-4804 Cell: 630-777-9291 On Mon, Mar 23, 2015 at 7:06 PM, George Skorup (Cyber Broadcasting) <[email protected]<mailto:[email protected]>> wrote: I have a problem site that we lose gear at every year (360' FM site). All of your guy wires are supposed to be bonded at the guy points (and the actual wires, not the pre-forms). And they're all broken every year. I've requested year after year that they do NOT use solid copper wire to tie all of the guys together. Instead, use like #6 or #4 stranded. But no, it doesn't happen. BTW, cadwelding is supposed to be done with nickel plated copper wire. And no, I would not attempt to cadweld to a Rohn 25 or 45 leg. The tubular legs are too thin and you'll burn through them. If you're using a base plate, that's probably OK. On 3/23/2015 4:01 PM, Ken Hohhof wrote: I was not aware you could cadweld to guy wires. From: Paul McCall<mailto:[email protected]> Sent: Monday, March 23, 2015 3:40 PM To: [email protected]<mailto:[email protected]> Subject: [AFMUG] Cad welding expert advice needed :) First foray into cad welding… actually my logistics guy is digging into it. We basically need to do 3 types of welding for towers. 1) Welding copper ground cable to the guy 3/16”, ¼” and 5/16” wires 2) Welding copper ground cable to ground rods 5/8” 3) Welding copper ground cable to Rohn 25G and 45G tower piece. Looking at lots of models, pieces parts. Anybody have some practical suggestions on pieces parts, vendors etc? Thanks! Paul McCall, Pres. PDMNet / Florida Broadband 658 Old Dixie Highway Vero Beach, FL 32962 772-564-6800<tel:772-564-6800> office 772-473-0352<tel:772-473-0352> cell www.pdmnet.com<http://www.pdmnet.com/> [email protected]<mailto:[email protected]>