On 6/8/15 14:57, Adam Moffett wrote:
I'm at a site where two towers are about 250' apart.  There's a 2"
conduit between the two towers, with nothing in it but a fiber optic
cable.  My tower does not have a generator, but the other one does. The
guy at the other tower offered to let me run electric off of a breaker
on his transfer panel so I could have a generator protected circuit.
This sounds great in theory, but I have a bad feeling about it because
(obviously) we have two separate electric services now and two separate
grounding systems.


Put an isolation transformer on it.

~Seth