On 10/07/2015 03:29 PM, Gino Villarini wrote:
no, will try-

On Wed, Oct 7, 2015 at 4:27 PM, Josh Baird <[email protected] <mailto:[email protected]>> wrote:

    Have you tried isolating the PTP600 with a DC/DC converter
    (Meanwell RSD, etc) in between the rectifier and PIDU?

    On Wed, Oct 7, 2015 at 4:24 PM, Gino Villarini
    <[email protected] <mailto:[email protected]>> wrote:

        ill check, but we did a bench test and it did not replicate
        the issue

        On Wed, Oct 7, 2015 at 4:19 PM, Chuck McCown <[email protected]
        <mailto:[email protected]>> wrote:

            If you put the PIDU and PTP600 on a cardboard box or other
            insulating surface, can you see –48 VDC on their cases or
            chassis?
            *From:* Gino Villarini <mailto:[email protected]>
            *Sent:* Wednesday, October 07, 2015 2:17 PM
            *To:* [email protected] <mailto:[email protected]>
            *Subject:* Re: [AFMUG] Issue with a -48 vdc Site! ground
            loop? Please Help!!
            i think so, afaik is floating ground
            On Wed, Oct 7, 2015 at 4:15 PM, Chuck McCown
            <[email protected] <mailto:[email protected]>> wrote:

                Is the chassis of the PIDU or the PTP600 connected to
                your common ground?
                *From:* Gino Villarini <mailto:[email protected]>
                *Sent:* Wednesday, October 07, 2015 2:14 PM
                *To:* [email protected] <mailto:[email protected]>
                *Subject:* [AFMUG] Issue with a -48 vdc Site! ground
                loop? Please Help!!
                So we are moving a site form AC to DC -48
                this is the setup:
                Emerson Rectifier feeding:
                Telco System MPLS router
                Planet Fiber SW
                2 Netonix DC Switches
                2 SAF POE Injectors
                2 PTP600 PIDUs
                AFAIK all the mentioned gear above are floating ground
                We have this gear connected to the Netonix:
                Airfiber24, Epmp, PMP450
                all wireless gear is using shielded cable that is
                terminated in a WBMGF SS on the rack
                So this is the issue, we migrated everything to DC,
                when we connect the PTP600 PIDU to the rectifier, the
                fuse on the emerson output feeding the Netonix
                blows..not instantly.. it takes some 30-45 secs..
                im scratching my head on this one... any ideas?