Does everything power normally prior to the fuse blowing? Does the ptp600
power and ping? Is the fuse properly sized?

On Wed, Oct 7, 2015 at 2:22 PM, David <[email protected]> wrote:

> We have to use the duracom dc dc isolators for them but no issues once we
> do it.
> Basically same thing using meanwell product.
>
>
>
>
> On 10/07/2015 03:29 PM, Gino Villarini wrote:
>
> no, will try-
>
> On Wed, Oct 7, 2015 at 4:27 PM, Josh Baird <[email protected]> wrote:
>
>> Have you tried isolating the PTP600 with a DC/DC converter (Meanwell RSD,
>> etc) in between the rectifier and PIDU?
>>
>> On Wed, Oct 7, 2015 at 4:24 PM, Gino Villarini <[email protected]>
>> wrote:
>>
>>> ill check, but we did a bench test and it did not replicate the issue
>>>
>>> On Wed, Oct 7, 2015 at 4:19 PM, Chuck McCown <[email protected]> wrote:
>>>
>>>> If you put the PIDU and PTP600 on a cardboard box or other insulating
>>>> surface, can you see –48 VDC on their cases or chassis?
>>>>
>>>> *From:* Gino Villarini <[email protected]>
>>>> *Sent:* Wednesday, October 07, 2015 2:17 PM
>>>> *To:* [email protected]
>>>> *Subject:* Re: [AFMUG] Issue with a -48 vdc Site! ground loop? Please
>>>> Help!!
>>>>
>>>> i think so, afaik is floating ground
>>>>
>>>> On Wed, Oct 7, 2015 at 4:15 PM, Chuck McCown <[email protected]> wrote:
>>>>
>>>>> Is the chassis of the PIDU or the PTP600 connected to your common
>>>>> ground?
>>>>>
>>>>> *From:* Gino Villarini <[email protected]>
>>>>> *Sent:* Wednesday, October 07, 2015 2:14 PM
>>>>> *To:* [email protected]
>>>>> *Subject:* [AFMUG] Issue with a -48 vdc Site! ground loop? Please
>>>>> Help!!
>>>>>
>>>>> So we are moving a site form AC to DC -48
>>>>>
>>>>> this is the setup:
>>>>>
>>>>> Emerson Rectifier feeding:
>>>>>
>>>>> Telco System MPLS router
>>>>> Planet Fiber SW
>>>>> 2 Netonix DC Switches
>>>>> 2 SAF POE Injectors
>>>>> 2 PTP600 PIDUs
>>>>>
>>>>> AFAIK all the mentioned gear above are floating ground
>>>>>
>>>>> We have this gear connected to the Netonix: Airfiber24, Epmp, PMP450
>>>>>
>>>>> all wireless gear is using shielded cable that is terminated in a
>>>>> WBMGF SS on the rack
>>>>>
>>>>> So this is the issue, we migrated everything to DC, when we connect
>>>>> the PTP600 PIDU to the rectifier, the fuse on the emerson output feeding
>>>>> the Netonix blows..not instantly.. it takes some 30-45 secs..
>>>>>
>>>>> im scratching my head on this one... any ideas?
>>>>>
>>>>>
>>>>>
>>>>
>>>>
>>>
>>>
>>
>
>