Ok. Will try firmware first. Thx Jaime Solorza
On Aug 1, 2017 9:38 PM, "Rory Conaway" <[email protected]> wrote: > We have seen weird issues with Toughswitches, most the 8-port versions > under heavy load. If it continues, try reloading the firmware first. If > that doesn’t work, try another switch, either a toughswitch or Netonix. > > > > Rory > > > > *From:* Af [mailto:[email protected]] *On Behalf Of *Jaime Solorza > *Sent:* Tuesday, August 1, 2017 7:38 PM > *To:* Animal Farm > *Subject:* [AFMUG] Stranger Things .... > > > > SCADA network with 31 Ubiquiti devices (AF5x, PB, NB, Cameras, NVR and > Toughswitches) and 52 devices like Phoenix Contact switches, Rockwell PLCs, > HMIs, Koyo , and Stratix router. Yesterday, a link was up but data > passing...they rebooted a Toughswitch and blowers in treatment plant turned > off where Stratix router is connected to this PLC. Toughswitch is powering > 6 cameras, one AP and last port connects to Phoenix Contact switch where > AF5X back haul is connected. Two PLCs and HMIs on same switch...we tested > the reboot scenario and it did shut down blowers. We broke the connection > between our Phoenix Contact switch and Stratix router and issue > disappeared. Our devices are on 192.168.1 x and blower room devices in > 10.10.254.x subnet. We are not responsible for Stratix and our SCADA > network doesn't currently poll any devices at this blower room. We got > everything back on line but with no physical connection between both, > rebooted Toughswitch and no more issue. We stopped due to thunderstorms, > but wondering if you guys have suggestions or ideas. Thanks > > Jaime Solorza >