Anyone,
Coming up on a design issue with our upcoming first deployment of Nexus
5010s and 5020s in a new datacenter. It's recommended in the following doc to
use the mgmt0 interface for peer keepalive messages:
http://www.cisco.com/en/US/docs/switches/datacenter/nexus5000/sw/layer2/Cisco_Nexus_5000_Series_NX-OS__chapter8.html#concept_47F7274E5FDA489884D0488BC491B066
We're doing a true out of band management approach on this new network, so the
mgmt0 interfaces all home back to an OOB switch/router (4507) which houses the
NMS gear, etc. My concern is that a reload (or failure of some type) on this
OOB switch could cause a 'dual active' situation on all the Nexus pairs of
devices . (6 pairs of 5010s, and the pair of 5020s that aggregate the 5010
pairs). I don't think I want that to happen. So the alternative seems to be a
back to back non-VPC-peer link between the two devices using a VLAN interface,
but I hate the idea of using a 10 gig port just for keepalives. There are what
appears to be additional copper mgmt ports on the boxes, but they're covered
up, and not in the CLI. Any way to utilize those? Any other possibilities I'm
overlooking? Or am I stuck getting 1 gig copper SFPs and crossover cables for
keepalives?
Thanks,
Chuck