Hi Frederic, First of all, a warm welcome here. I am sorry to hear that you are having trouble. If course it could be that the hardware is causing trouble. I guess the only way to find out what's going wrong would be to do a Wireshark recording of the communication.
Then we can be sure what's going wrong. The discarded incoming message, is definitely the cause, but I don't know what could be causing this. Could you do a Wireshark capture, create a jira issue and attach it to that? Then I'll have a look. Chris ________________________________ Von: Fr?d?ric Auberson <[email protected]> Gesendet: Montag, 11. November 2019 14:52:44 An: [email protected] <[email protected]> Betreff: "Discarded Message"... How do I start debugging this? Hi All, I'm trying to make my first steps, but already hitting a roadblock: My minimal code seems stuck on getConnection, and I've no idea how to debug this. I'm really trying to do something minimal, inspired by the example code, and reading the first 4 input pins of my S7-200. I see the "START" log entry, but not the "CONNECTED" one, meaning I never complete the connection step. The only suspicious thing I see is this: Discarded message pipeline : [S7PlcConnection$1$1#0, IsoOnTcpProtocol#0, IsoTPProtocol#0, S7Protocol#0, Plc4XS7Protocol#0, DefaultChannelPipeline$TailContext#0]. Channel : [id: 0x5148d82b, L:/ 192.168.1.16:53396 - R:/192.168.1.222:102]." Full disclosure: I'm using an off-brand adapter because I can't afford a proper Siemens CP 243-1. Can that cause the issue? How do I even begin to debug this? Thanks, Fred ----- my code ----- static final String connectionString = "s7://192.168.1.222/0/2"; public static void main(String[] args) { logger.info("----- START -----"); try (PlcConnection plcConnection = new PlcDriverManager().getConnection(connectionString)) { logger.info("----- CONNECTED -----"); if (!plcConnection.getMetadata().canRead()) { logger.error("This connection doesn't support reading."); return; } PlcReadRequest.Builder builder = plcConnection.readRequestBuilder(); builder.addItem("value-1", "%I0.0:BOOL"); builder.addItem("value-2", "%I0.1:BOOL"); builder.addItem("value-3", "%I0.2:BOOL"); builder.addItem("value-4", "%I0.3:BOOL"); PlcReadRequest readRequest = builder.build(); logger.info(readRequest.execute().get().toString()); logger.info("----- DONE -----"); } catch (Exception e) { e.printStackTrace(); } ----- the output ----- INFO S7Test - ----- START ----- INFO o.apache.plc4x.java.PlcDriverManager - Instantiating new PLC Driver Manager with class loader sun.misc.Launcher$AppClassLoader@18b4aac2 INFO o.apache.plc4x.java.PlcDriverManager - Registering available drivers... INFO o.apache.plc4x.java.PlcDriverManager - Registering driver for Protocol s7 (Siemens S7 (Basic)) DEBUG i.n.u.i.l.InternalLoggerFactory - Using SLF4J as the default logging framework DEBUG io.netty.util.ResourceLeakDetector - -Dio.netty.leakDetection.level: simple [...lots of Netty debug output removed here...] DEBUG io.netty.util.Recycler - -Dio.netty.recycler.ratio: 8 DEBUG o.a.p.j.i.protocol.IsoOnTcpProtocol - ISO on TCP Message sent DEBUG o.a.p.j.i.protocol.IsoOnTcpProtocol - ISO on TCP Message received DEBUG o.a.p.j.isotp.protocol.IsoTPProtocol - Got Data: 11d00001000200c2020200c1020102c0010a DEBUG o.a.plc4x.java.s7.netty.S7Protocol - S7 Message with id 0 queued DEBUG o.a.p.j.i.protocol.IsoOnTcpProtocol - ISO on TCP Message sent DEBUG o.a.plc4x.java.s7.netty.S7Protocol - S7 Message with id 0 sent DEBUG i.n.channel.DefaultChannelPipeline - Discarded inbound message org.apache.plc4x.java.isotp.protocol.model.IsoTPMessage@480c8d80 that reached at the tail of the pipeline. Please check your pipeline configuration. DEBUG i.n.channel.DefaultChannelPipeline - Discarded message pipeline : [S7PlcConnection$1$1#0, IsoOnTcpProtocol#0, IsoTPProtocol#0, S7Protocol#0, Plc4XS7Protocol#0, DefaultChannelPipeline$TailContext#0]. Channel : [id: 0x5148d82b, L:/192.168.1.16:53396 - R:/192.168.1.222:102]. DEBUG o.a.p.j.i.protocol.IsoOnTcpProtocol - ISO on TCP Message received DEBUG o.a.p.j.isotp.protocol.IsoTPProtocol - Got Data: 02f080320300000000000800000000f0010001000100f0 INFO o.a.plc4x.java.s7.netty.S7Protocol - S7Connection established pdu-size 240, max-amq-caller 1, max-amq-callee 1 DEBUG o.a.plc4x.java.s7.netty.S7Protocol - S7 Message with id 2 queued DEBUG o.a.plc4x.java.s7.netty.S7Protocol - S7 Message with id 0 received DEBUG o.a.p.j.i.protocol.IsoOnTcpProtocol - ISO on TCP Message sent DEBUG o.a.plc4x.java.s7.netty.S7Protocol - S7 Message with id 2 sent DEBUG i.n.channel.DefaultChannelPipeline - Discarded inbound message org.apache.plc4x.java.isotp.protocol.model.IsoTPMessage@64b0dea4 that reached at the tail of the pipeline. Please check your pipeline configuration. DEBUG i.n.channel.DefaultChannelPipeline - Discarded message pipeline : [S7PlcConnection$1$1#0, IsoOnTcpProtocol#0, IsoTPProtocol#0, S7Protocol#0, Plc4XS7Protocol#0, DefaultChannelPipeline$TailContext#0]. Channel : [id: 0x5148d82b, L:/192.168.1.16:53396 - R:/192.168.1.222:102].