>I'm still puzzled, since small delays don't work for me either. And I do work >the third (vdd) line. When the conversion is running and I read the device, >the reported temperature is 85 degrees. So I have to wait for 800ms - one way >or the other - after conversion before I can get a valid reading.
Just some thoughts... If you're reading only occasionally, do this: - start conversion - wait some time, depending on selected resolution - read value If you're reading continuously, do this: - read value from last conversion - start new conversion - rely on the main program not to read again before the conversion has finished Greets, Kiste -- You received this message because you are subscribed to the Google Groups "jallib" group. To post to this group, send email to [email protected]. To unsubscribe from this group, send email to [email protected]. For more options, visit this group at http://groups.google.com/group/jallib?hl=en.