Hi,

On Tue, May 04, 2010 at 01:21:44PM -0600, Greg Woods wrote:
> We have a pair of servers in a cluster plugged into a pair of APC
> rack-mounted PDU's of the sort that could be controlled by this stonith
> plugin. My problem is that these are dual power supply servers, which
> means I would have to shut down two outlets that are on on two different
> PDUs to completely power off one of the nodes. Is it possible to use
> this stonith plugin to do that? The documentation on configuring outlet
> numbers (from "crm ra info stonith:external/rackpdu") is a bit sparse;
> it isn't clear that what I want to do is even possible.

No, rackpdu doesn't support multiple outlet reset. We do accept
patches though :) The plugin is implemented in shell, shouldn't
be too difficult to modify.

If these servers have a lights-out device and the power
distribution is fairly reliable, that could be an alternative for
fencing.

Thanks,

Dejan

> 