I'm not sure what you mean by having losses "not be taken into consideration by 
the opf" without "eliminating" them. I don't think you can have it both ways. 
If you want an OPF based on a lossless approximation to the network, I see two 
options … (1) a DC OPF or (2) an AC OPF with the branch resistances set to zero.

-- 
Ray Zimmerman
Senior Research Associate
B30 Warren Hall, Cornell University, Ithaca, NY 14853
phone: (607) 255-9645





On Jul 10, 2013, at 2:46 PM, Dionisis Stamatiadis <[email protected]> 
wrote:

> Hi All, 
> I was wondering if is there any way to exclude the losses when running an 
> opf. I do not want to eliminate the losses (R=0 X=0) but to not be taken into 
> consideration by the opf.
> Thank you, 
> Dionisis                                        
> 