No, that is not currently implemented. However, you could use the OPF to solve
a constrained power flow, by setting the voltage magnitude and active power
limits at PV buses to their set-points. The voltage magnitude limits at the
slack bus also need to be set to the voltage setpoint.
Ray
> On Jun 1, 2016, at 3:40 PM, Zhi Zhang <[email protected]> wrote:
>
> Hi everyone,
>
> Is it possible to use generator capability curve with runpf? I know it works
> with opf, but I am wondering if I can somehow use it with runpf.
>
> Thank you!
> Justin