> I'm only really interested in seeing the Temp being graphed at this > time... so is there a way to remove the humidity and just see the temp??
I'll do you one better -- how about two targets, one for the humidity and one for the temperature? It could also be done with both targets on the same graph if you wanted. > WorkDir: /var/www/html/mrtg [..snip..] > WithPeak[10.35.60.33_1]: ymw Excuse my mailer's hatred and butchery of long lines. Title[apc_temp]: Temperature for IT Server Room PageTop[apc_temp]: <H1>Temperature in IT Server Room</H1> Target[apc_temp]: 1.3.6.1.4.1.318.1.1.2.1.1.0&PseudoZero:[EMAIL PROTECTED]: * 1.8 + 32 MaxBytes[apc_temp]: 100 Options[apc_temp]: growright,gauge,nopercent,noo YLegend[apc_temp]: Temp ShortLegend[apc_temp]: deg F Legend1[apc_temp]: Temperature Legend2[apc_temp]: Legend3[apc_temp]: Max Temp. value per interval on graph Legend4[apc_temp]: LegendI[apc_temp]: Sensor Temp: LegendO[apc_temp]: Colours[apc_temp]: BLUE#0000ff,GREEN#00eb0c,GRAY#AAAAAA,VIOLET#ff00ff Title[apc_humi]: Humidity in IT Server Room PageTop[apc_humi]: <H1>Humidity in IT Server Room</H1> Target[apc_humi]: 1.3.6.1.4.1.318.1.1.2.1.2.0&PseudoZero:[EMAIL PROTECTED]: MaxBytes[apc_humi]: 100 Options[apc_humi]: growright,gauge,nopercent,noo YLegend[apc_humi]: Humidity ShortLegend[apc_humi]: in Hg Legend1[apc_humi]: humidity Legend2[apc_humi]: Legend3[apc_humi]: Max Humidity value per interval on graph Legend4[apc_humi]: LegendI[apc_humi]: Sensor Humidity: LegendO[apc_humi]: Colours[apc_humi]: BLUE#0000FF,GREEN#00eb0c,GRAY#AAAAAA,VIOLET#ff00ff that should do the trick. If you want to do them both on the same target it's a little trickier; let me know and i'll fix0r a config file for you :) cheers -kelsey -- Unsubscribe mailto:[EMAIL PROTECTED] Archive http://lists.ee.ethz.ch/mrtg FAQ http://faq.mrtg.org Homepage http://www.mrtg.org WebAdmin http://lists.ee.ethz.ch/lsg2.cgi