Hi UPS List members, I have purchased a number of Emerson Power / Liebert GXT4 UPS units. I have these working correctly under nut, but limited detsils are being reported. I am happy to supply information on the USB communications to improve the reported details I can use WireShark to capture the comms between the supplied Windows GUI tool and the UPS Please advise the best way I can help. In the meantime, The output of: /sbin/usbhid-ups -DD -a liebert -i 120 | tee /tmp/liebert-GXT4.txt
is attached STDOUT: Network UPS Tools - Generic HID driver 0.37 (2.6.5) USB communication driver 0.31 STDERR Attached: /tmp/liebert-GXT4.txt -- Regards, Christo Simeonoff, Technical Director, Integrity Net P/L Ph: (02) 8012 5115 M: (04) 19 992 965 F: (02) 99070990 E: integrity...@iinet.net.au
0.000000 debug level is '2' 0.000558 upsdrv_initups... 0.003256 Checking device (10AF/0000) (001/004) 0.004504 - VendorID: 10af 0.004536 - ProductID: 0000 0.004555 - Manufacturer: Emerson Network Power 0.004574 - Product: Liebert GXT4 0.004597 - Serial Number: ZZZZZZZZZZZZZZZ 0.004613 - Bus: 001 0.004630 Trying to match device 0.004678 Device matches 0.004705 failed to claim USB device: could not claim interface 0: Device or resource busy 0.004740 detached kernel driver from USB device... 0.005265 HID descriptor length 505 0.007255 Report Descriptor size = 505 0.007544 Using subdriver: Belkin HID 0.15 0.007767 Path: UPS.PowerSummary.Undefined, Type: Feature, ReportID: 0x01, Offset: 0, Size: 8, Value: 0 0.008018 Path: UPS.PowerSummary.iSerialNumber, Type: Feature, ReportID: 0x02, Offset: 0, Size: 4, Value: 3 0.008049 Path: UPS.PowerSummary.iManufacturer, Type: Feature, ReportID: 0x02, Offset: 4, Size: 4, Value: 1 0.008078 Path: UPS.PowerSummary.iOEMInformation, Type: Feature, ReportID: 0x02, Offset: 8, Size: 4, Value: 1 0.008109 Path: UPS.PowerSummary.iDeviceChemistry, Type: Feature, ReportID: 0x02, Offset: 12, Size: 4, Value: 6 0.008146 Path: UPS.PowerSummary.DesignCapacity, Type: Feature, ReportID: 0x02, Offset: 16, Size: 8, Value: 100 0.008390 Path: UPS.PowerSummary.RemainingTimeLimit, Type: Feature, ReportID: 0x03, Offset: 0, Size: 24, Value: 250 0.008419 Path: UPS.PowerSummary.CapacityMode, Type: Feature, ReportID: 0x03, Offset: 24, Size: 2, Value: 2 0.008448 Path: UPS.PowerSummary.Rechargeable, Type: Feature, ReportID: 0x03, Offset: 26, Size: 1, Value: 1 0.008480 Path: UPS.PowerSummary.Undefined, Type: Feature, ReportID: 0x03, Offset: 27, Size: 5, Value: 1 0.008638 Path: UPS.PowerSummary.RemainingCapacityLimit, Type: Feature, ReportID: 0x13, Offset: 0, Size: 8, Value: 20 0.008892 Path: UPS.PowerSummary.RemainingCapacity, Type: Feature, ReportID: 0x06, Offset: 0, Size: 8, Value: 100 0.008921 Path: UPS.PowerSummary.RemainingCapacity, Type: Input, ReportID: 0x06, Offset: 0, Size: 8, Value: 100 0.009139 Path: UPS.PowerSummary.Charging, Type: Feature, ReportID: 0x0c, Offset: 0, Size: 1, Value: 1 0.009168 Path: UPS.PowerSummary.Discharging, Type: Feature, ReportID: 0x0c, Offset: 1, Size: 1, Value: 0 0.009195 Path: UPS.PowerSummary.ACPresent, Type: Feature, ReportID: 0x0c, Offset: 2, Size: 1, Value: 1 0.009226 Path: UPS.PowerSummary.BelowRemainingCapacityLimit, Type: Feature, ReportID: 0x0c, Offset: 3, Size: 1, Value: 0 0.009250 Path: UPS.PowerSummary.BatteryPresent, Type: Feature, ReportID: 0x0c, Offset: 4, Size: 1, Value: 1 0.009274 Path: UPS.PowerSummary.Undefined, Type: Feature, ReportID: 0x0c, Offset: 5, Size: 3, Value: 0 0.009298 Path: UPS.PowerSummary.Charging, Type: Input, ReportID: 0x0c, Offset: 0, Size: 1, Value: 1 0.009334 Path: UPS.PowerSummary.Discharging, Type: Input, ReportID: 0x0c, Offset: 1, Size: 1, Value: 0 0.009358 Path: UPS.PowerSummary.ACPresent, Type: Input, ReportID: 0x0c, Offset: 2, Size: 1, Value: 1 0.009382 Path: UPS.PowerSummary.BelowRemainingCapacityLimit, Type: Input, ReportID: 0x0c, Offset: 3, Size: 1, Value: 0 0.009411 Path: UPS.PowerSummary.BatteryPresent, Type: Input, ReportID: 0x0c, Offset: 4, Size: 1, Value: 1 0.009442 Path: UPS.PowerSummary.Undefined, Type: Input, ReportID: 0x0c, Offset: 5, Size: 3, Value: 0 0.009642 Path: UPS.PowerSummary.FullChargeCapacity, Type: Feature, ReportID: 0x04, Offset: 0, Size: 8, Value: 0 0.009673 Path: UPS.PowerSummary.WarningCapacityLimit, Type: Feature, ReportID: 0x04, Offset: 8, Size: 8, Value: 0 0.009702 Path: UPS.PowerSummary.CapacityGranularity1, Type: Feature, ReportID: 0x04, Offset: 16, Size: 8, Value: 1 0.009731 Path: UPS.PowerSummary.CapacityGranularity2, Type: Feature, ReportID: 0x04, Offset: 24, Size: 8, Value: 1 0.010016 Path: UPS.PowerSummary.Voltage, Type: Feature, ReportID: 0x05, Offset: 0, Size: 16, Value: 0 0.010047 Path: UPS.PowerSummary.ConfigVoltage, Type: Feature, ReportID: 0x05, Offset: 16, Size: 16, Value: 0 0.010260 Path: UPS.PowerSummary.Test, Type: Feature, ReportID: 0x08, Offset: 0, Size: 8, Value: 0 0.010511 Path: UPS.PowerSummary.Undefined, Type: Feature, ReportID: 0x09, Offset: 0, Size: 8, Value: 0 0.010760 Path: UPS.PowerSummary.Undefined, Type: Feature, ReportID: 0x32, Offset: 0, Size: 8, Value: 1 0.011002 refresh_report_buffer: expected 5 bytes, but got 2 instead 0.011031 Path: UPS.PowerSummary.Undefined, Type: Feature, ReportID: 0x33, Offset: 0, Size: 8, Value: 1 0.011264 Path: UPS.PowerSummary.iProduct, Type: Feature, ReportID: 0x07, Offset: 0, Size: 8, Value: 0 0.011512 Path: UPS.PowerSummary.Undefined, Type: Feature, ReportID: 0x3c, Offset: 0, Size: 8, Value: 0 0.011761 Path: UPS.PowerSummary.Undefined, Type: Feature, ReportID: 0x3d, Offset: 0, Size: 8, Value: 0 0.012015 Path: UPS.PowerSummary.Undefined, Type: Feature, ReportID: 0x3e, Offset: 0, Size: 8, Value: 1 0.012263 Path: UPS.PowerSummary.Undefined, Type: Feature, ReportID: 0x3f, Offset: 0, Size: 8, Value: 0 0.012512 Path: UPS.PowerSummary.Undefined, Type: Feature, ReportID: 0x40, Offset: 0, Size: 8, Value: 0 0.012762 Path: UPS.PowerSummary.Undefined, Type: Feature, ReportID: 0x41, Offset: 0, Size: 8, Value: 0 0.013012 Path: UPS.PowerSummary.Undefined, Type: Feature, ReportID: 0x42, Offset: 0, Size: 8, Value: 1 0.013264 Path: UPS.PowerSummary.Undefined, Type: Feature, ReportID: 0x43, Offset: 0, Size: 8, Value: 1 0.013512 Path: UPS.PowerSummary.Undefined, Type: Feature, ReportID: 0x44, Offset: 0, Size: 8, Value: 1 0.013762 Path: UPS.PowerSummary.Undefined, Type: Feature, ReportID: 0x50, Offset: 0, Size: 8, Value: 0 0.014014 Path: UPS.PowerSummary.Undefined, Type: Feature, ReportID: 0x51, Offset: 0, Size: 8, Value: 0 0.014261 Path: UPS.PowerSummary.Undefined, Type: Feature, ReportID: 0x52, Offset: 0, Size: 8, Value: 0 0.014510 Path: UPS.PowerSummary.Undefined, Type: Feature, ReportID: 0x53, Offset: 0, Size: 8, Value: 0 0.014760 Path: UPS.PowerSummary.Undefined, Type: Feature, ReportID: 0x54, Offset: 0, Size: 8, Value: 0 0.015011 Path: UPS.PowerSummary.Undefined, Type: Feature, ReportID: 0x55, Offset: 0, Size: 8, Value: 0 0.015264 Path: UPS.PowerSummary.Undefined, Type: Feature, ReportID: 0x56, Offset: 0, Size: 8, Value: 1 0.015513 Path: UPS.PowerSummary.Undefined, Type: Feature, ReportID: 0x57, Offset: 0, Size: 8, Value: 0 0.015762 Path: UPS.PowerSummary.Undefined, Type: Feature, ReportID: 0x58, Offset: 0, Size: 8, Value: 1 0.016014 Path: UPS.PowerSummary.Undefined, Type: Feature, ReportID: 0x59, Offset: 0, Size: 8, Value: 0 0.016263 Path: UPS.PowerSummary.Undefined, Type: Feature, ReportID: 0x5a, Offset: 0, Size: 8, Value: 1 0.016512 Path: UPS.PowerSummary.Undefined, Type: Feature, ReportID: 0x5b, Offset: 0, Size: 8, Value: 1 0.016762 Path: UPS.PowerSummary.Undefined, Type: Feature, ReportID: 0x5c, Offset: 0, Size: 8, Value: 0 0.017014 Path: UPS.PowerSummary.Undefined, Type: Feature, ReportID: 0x5d, Offset: 0, Size: 8, Value: 0 0.017054 Report descriptor retrieved (Reportlen = 505) 0.017073 Found HID device 0.017098 Detected a UPS: Emerson Network Power/Liebert GXT4 0.017148 Path: UPS.PowerSummary.RemainingCapacityLimit, Type: Feature, ReportID: 0x13, Offset: 0, Size: 8, Value: 20 0.017184 Path: UPS.PowerSummary.WarningCapacityLimit, Type: Feature, ReportID: 0x04, Offset: 8, Size: 8, Value: 0 0.017225 Path: UPS.PowerSummary.iDeviceChemistry, Type: Feature, ReportID: 0x02, Offset: 12, Size: 4, Value: 6 0.017676 Path: UPS.PowerSummary.RemainingCapacity, Type: Feature, ReportID: 0x06, Offset: 0, Size: 8, Value: 100 0.017725 Path: UPS.PowerSummary.Voltage, Type: Feature, ReportID: 0x05, Offset: 0, Size: 16, Value: 0 0.017746 Input/OutputVoltage = 0 -> assuming correction factor = 1e+07 0.017779 Path: UPS.PowerSummary.ConfigVoltage, Type: Feature, ReportID: 0x05, Offset: 16, Size: 16, Value: 0 0.017799 ConfigVoltage = 0 -> assuming correction factor = 1e+08 0.017837 Path: UPS.PowerSummary.Discharging, Type: Feature, ReportID: 0x0c, Offset: 1, Size: 1, Value: 0 0.017873 Path: UPS.PowerSummary.Charging, Type: Feature, ReportID: 0x0c, Offset: 0, Size: 1, Value: 1 0.017910 Path: UPS.PowerSummary.ACPresent, Type: Feature, ReportID: 0x0c, Offset: 2, Size: 1, Value: 1 0.018090 find_nut_info: unknown info type: load.off.delay 0.018112 find_nut_info: unknown info type: load.on.delay 0.018133 find_nut_info: unknown info type: load.off.delay 0.018159 upsdrv_initinfo... 0.018189 upsdrv_updateinfo... 0.079719 Got 6 HID objects... 0.079755 Path: UPS.PowerSummary.Charging, Type: Input, ReportID: 0x0c, Offset: 0, Size: 1, Value: 1 0.079786 Path: UPS.PowerSummary.Discharging, Type: Input, ReportID: 0x0c, Offset: 1, Size: 1, Value: 0 0.079816 Path: UPS.PowerSummary.ACPresent, Type: Input, ReportID: 0x0c, Offset: 2, Size: 1, Value: 1 0.079842 Path: UPS.PowerSummary.BelowRemainingCapacityLimit, Type: Input, ReportID: 0x0c, Offset: 3, Size: 1, Value: 0 0.079875 Path: UPS.PowerSummary.BatteryPresent, Type: Input, ReportID: 0x0c, Offset: 4, Size: 1, Value: 1 0.079901 Path: UPS.PowerSummary.Undefined, Type: Input, ReportID: 0x0c, Offset: 5, Size: 3, Value: 0 0.079920 Quick update... 0.079944 Path: UPS.PowerSummary.RemainingCapacity, Type: Feature, ReportID: 0x06, Offset: 0, Size: 8, Value: 100 0.079968 Path: UPS.PowerSummary.Discharging, Type: Feature, ReportID: 0x0c, Offset: 1, Size: 1, Value: 0 0.079990 Path: UPS.PowerSummary.Charging, Type: Feature, ReportID: 0x0c, Offset: 0, Size: 1, Value: 1 0.080012 Path: UPS.PowerSummary.ACPresent, Type: Feature, ReportID: 0x0c, Offset: 2, Size: 1, Value: 1 0.080132 dstate_init: sock /var/run/nut/usbhid-ups-liebertA open on fd 5 0.080163 upsdrv_updateinfo... 0.112015 Got 1 HID objects... 0.112051 Path: UPS.PowerSummary.RemainingCapacity, Type: Input, ReportID: 0x06, Offset: 0, Size: 8, Value: 100 0.112075 Quick update... 0.112106 Path: UPS.PowerSummary.RemainingCapacity, Type: Feature, ReportID: 0x06, Offset: 0, Size: 8, Value: 100 0.112130 Path: UPS.PowerSummary.Discharging, Type: Feature, ReportID: 0x0c, Offset: 1, Size: 1, Value: 0 0.112152 Path: UPS.PowerSummary.Charging, Type: Feature, ReportID: 0x0c, Offset: 0, Size: 1, Value: 1 0.112173 Path: UPS.PowerSummary.ACPresent, Type: Feature, ReportID: 0x0c, Offset: 2, Size: 1, Value: 1
_______________________________________________ Nut-upsdev mailing list Nut-upsdev@lists.alioth.debian.org http://lists.alioth.debian.org/cgi-bin/mailman/listinfo/nut-upsdev