Hi Jan, Many thanks for your words of wisdom, I will take them on board.
You say that the DS2482-800 can reset to an unusable state, would the same apply to the DS2482-100? Sheepwalk now make a dual channel RPi2 and I could stack 2 to get 4 channels and I think I could manage with that if the lock up problem is fixed.
Thanks Mick On 20/10/2018 18:00, Jan Kandziora wrote:
About the bus lock-up, that's a bug in the DS2482-800, I think. I had it. Various other people had it. The DS2482-800 seems to be susceptible to supply undervoltage and slow rising of the supply voltage. It resets into an unuseable state. Only a complete power-down and quick power-on will make it useable again. Kind regards Jan
_______________________________________________ Owfs-developers mailing list Owfs-developers@lists.sourceforge.net https://lists.sourceforge.net/lists/listinfo/owfs-developers