[Emc-users] 3 phase power

2011-11-10 Thread Brian May
This is probably an easy question for alot af the people on the list. I have 3 phase power going to my vfd on my machine. I want to the use that same power to power all the 120 single phase components. (the dc power supply for the steppers and varios other motors. ). This way i only need 1

Re: [Emc-users] 3 phase power

2011-11-10 Thread Eric Keller
the lights and most outlets here at work are single phase wired off of 3 phase. On Thu, Nov 10, 2011 at 9:50 PM, Brian May bri...@diezorlich.com wrote: This is probably an easy question for alot af the people on the list. I have 3 phase power going to my vfd on my machine. I want to the use

Re: [Emc-users] 3 phase power

2011-11-10 Thread Brian May
Yes everything at our shop is wired off 3 phase. But our box has a nuetral. So it goes from leg to nuetral. However my machine only has 4 lines - the 3 legs of power and an earth ground. So i guess my question is do i need the nuetral? Sent from my iPod On Nov 10, 2011, at 8:59 PM, Eric Keller

Re: [Emc-users] 3 phase power

2011-11-10 Thread Karl Cunningham
On 11/10/2011 06:50 PM, Brian May wrote: This is probably an easy question for alot af the people on the list. I have 3 phase power going to my vfd on my machine. I want to the use that same power to power all the 120 single phase components. (the dc power supply for the steppers and varios

Re: [Emc-users] 3 phase power

2011-11-10 Thread Brian Mihulka
On 11/10/2011 08:50 PM, Brian May wrote: This is probably an easy question for alot af the people on the list. I have 3 phase power going to my vfd on my machine. I want to the use that same power to power all the 120 single phase components. (the dc power supply for the steppers and

Re: [Emc-users] 3 phase power

2011-11-10 Thread Brian May
Ok that makes sense. Just out of curiosity, How do other machines do it. Our other cnc machines only have the 3 lines and earth ground running into them... Sent from my iPod On Nov 10, 2011, at 9:01 PM, Brian Mihulka bmihu...@hulkster.net wrote: On 11/10/2011 08:50 PM, Brian May wrote:

Re: [Emc-users] 3 phase power

2011-11-10 Thread Terry Christophersen
You need a transformer to step it down,that is how most machines do it. this will be a cleaner set up rather than 3ph and a 1ph line coming in.   From: Brian May bri...@diezorlich.com To: Enhanced Machine Controller (EMC) emc-users@lists.sourceforge.net Sent:

Re: [Emc-users] 3 phase power

2011-11-10 Thread Dave
Usually bigger 3 phase machines being fed with 480 volts or so will only have the 3 phases run to the machine without a neutral wire. The reason being that Line to Neutral on a 480 volt system is 277 volts and that is not very useful for anything other than lighting. To get 120 VAC, two of the