Hi Josh,
Try adding:
10,/
to the RPN field of the DataPoint. The format field is used to do the
summary reports at the bottom.
-Eric
Baird, Josh wrote:
I am graphing current voltage output of my UPS. The OID returns:
.1.3.6.1.2.1.33.1.2.5.0 = INTEGER: 3268 (326.8volts), however the
DataPoint is actually displaying as 3.26k). I have tried changing the
'Format' field of the DataPoint to no avail. Does anyone know how to
change this?
Using 1.1...
Thanks,
Josh
------------------------------------------------------------------------