I am graphing current voltage output of my UPS.  The OID returns:

.1.3.6.1.2.1.33.1.2.5.0 = INTEGER: 3268 (326.8volts), however the DataPoint
is actually displaying as 3.26k).  I have tried changing the 'Format' field
of the DataPoint to no avail.  Does anyone know how to change this?

Josh,

You need to do two things for this to display properly. First, scale
it properly by setting the RPN to ".1,*" to divide it by 10. Second,
get rid of the units and lower the precision by changing the format to
"%0.1lf"

A better explanation of the possibilities is in the RRDTool
documentation. Specifically:
http://oss.oetiker.ch/rrdtool/doc/rrdgraph_graph.en.html

--
Chet Luther
[EMAIL PROTECTED]