Hello, I have one UPS Infosec XP Pro 2500 RM and it works with windows sw RUPS2000. Now I want to install this UPS as virtual server on vmware ESXi vMA - (SUSE SLES 11SP2 linux). On this linux I have NUT 2.6.0 and I stopped now with configuration of genericups driver.
Working cable (direct cable pin1-pin1 ... pin9-pin9) connection on Windows: PIN | PC | UPS __________________________________________________________________________________ Pin1 | DCD | described as DTR (must keep Hi) Pin2 | RxD | AC Power fail (NO, connected to pin4 UPS ground in case of AC failure) Pin3 | TxD | N/A Pin4 | DTR | UPS ground Pin5 | GND | Battery low (NO, connected to pin4 UPS ground in case of LB) Pin6 | DSR | 1. described as UPS RxD and 2. 3 seconds Hi (UPS shutdown) Pin7 | RTS | UPS ground Pin8 | CTS | N/A Pin9 | RI | described as UPS TxD And the question is, how to configure CP[???], OL[???], LB[???], SD[???]? No one from predefined 21 types worked for me. Thank for help, Robert SZAKSZ. _______________________________________________ Nut-upsuser mailing list Nut-upsuser@lists.alioth.debian.org http://lists.alioth.debian.org/cgi-bin/mailman/listinfo/nut-upsuser