Definitely. A 2/0 or larger exothermically welded to a top mounted ground rod to the ground system at bottom improves conducting strikes to earth greatly. Counting on tower sections to conduct the strike to ground is unreliable at best.
On Sun, Sep 29, 2019, 12:32 PM Matt <matt.mailingli...@gmail.com> wrote: > I have seen some towers that have a copper ground wire run all the way > to top of tower. Is there any real benefit in this for lightning > protection? > > -- > AF mailing list > AF@af.afmug.com > http://af.afmug.com/mailman/listinfo/af_af.afmug.com >
-- AF mailing list AF@af.afmug.com http://af.afmug.com/mailman/listinfo/af_af.afmug.com