On 10/3/2011 3:43 AM, andy pugh wrote: > On 3 October 2011 08:29, Sven Wesley<svenne.d...@gmail.com> wrote: > > >> At the same time, An extremely expensive Siemens VFD fired off the RCD... >> > That is probably because the Siemens VFD includes an input-side > filter. Unfortunately filters provide a path to earth, and RCDs are > designed to detect that. > > I thought that EU standards dictated the use of input side filters.. yet they trip your RCDs.. so how does that work in real life?
Are RCDs not required in factories? Dave ------------------------------------------------------------------------------ All the data continuously generated in your IT infrastructure contains a definitive record of customers, application performance, security threats, fraudulent activity and more. Splunk takes this data and makes sense of it. Business sense. IT sense. Common sense. http://p.sf.net/sfu/splunk-d2dcopy1 _______________________________________________ Emc-users mailing list Emc-users@lists.sourceforge.net https://lists.sourceforge.net/lists/listinfo/emc-users